Full-Scale Fire Experiment on Mezzanine Racks in Logistics Facilities

Byeongheun Lee, Nam Jeon, Jeongki Min

Fire · 20.09.2024 · 7 (9) · 326

DOI: 10.3390/fire7090326 ↗

Kurz gefasst

Fachartikel in der Zeitschrift Fire, online erschienen am 20.09.2024. Verfasst von Byeongheun Lee und 2 weiteren Autor:innen. Die Arbeit wurde bisher 5-mal zitiert (Crossref) und nennt 18 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0). Gefördert von: Korea Agency for Infrastructure Technology Advancement (KAIA).

AbstractBibliografische AngabenZitierenVerwandte Studien

Abstract (Originalsprache)

The increased demand for contactless services has facilitated a rapid increase in logistics facilities. There are shorter distances between the shelf racks used in mezzansine racks in such facilities compared to standard racks and can store various items; however, research on fire safety related to this remains insufficient. In this study, we visited four logistics facilities with mezzanine racks and one logistics facility using shelf racks to investigate their fundamental characteristics. Considering the characteristics of logistics facilities that store various combustibles, a fire test was conducted using unit shelf racks with packaging materials, boxes, and expandable polystyrene (EPS). Shelf racks loaded with corrugated fiberboard, cardboard boxes, and EPS exhibited the highest fire risk and were set as combustibles inside the rack. Before the experiment, the radiative heat flux was measured by considering the spacing distances of mezzanine racks observed on-site. The most frequently measured range was 43.7–67.3 kW/m2 at 1.0–1.5 m. After beginning the fire experiment, when simulating mezzanine racks with aisle widths of 1.2–2.0 m, fire owing to radiative heat occurred within 5 min in the separated shelf racks. Based on the results, we estimate that the minimum separation distance required to prevent radiant heat-based fires between shelving racks inside a mezzanine is 3.2 m. These findings are expected to be utilized in fire prevention by increasing the understanding of the spread of fire in shelf racks.

Förderung

  • Korea Agency for Infrastructure Technology Advancement (KAIA)

Zitieren

APA

Lee, B., Jeon, N., & Min, J. (2024). Full-Scale Fire Experiment on Mezzanine Racks in Logistics Facilities. Fire, 7(9), 326. https://doi.org/10.3390/fire7090326

Vancouver

Lee B, Jeon N, Min J. Full-Scale Fire Experiment on Mezzanine Racks in Logistics Facilities. Fire. 2024;7(9):326. doi:10.3390/fire7090326

BibTeX
@article{Lee2024,
  author = {Lee, Byeongheun and Jeon, Nam and Min, Jeongki},
  title = {Full-Scale Fire Experiment on Mezzanine Racks in Logistics Facilities},
  journal = {Fire},
  year = {2024},
  volume = {7},
  number = {9},
  pages = {326},
  doi = {10.3390/fire7090326}
}
Kostenlos starten →