Experimental Study on Fire Suppression of the Outdoor Oil-Immersed Transformer by High-Pressure Water Mist System
Fire · 15.06.2023 · 6 (6) · 238
DOI: 10.3390/fire6060238 ↗Kurz gefasst
Fachartikel in der Zeitschrift Fire, online erschienen am 15.06.2023. Verfasst von Huaitao Song und 6 weiteren Autor:innen. Die Arbeit wurde bisher 9-mal zitiert (Crossref) und nennt 51 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0). Gefördert von: National Natural Science Foundation of China, Henan Provincial Science and Technology Research Project.
Abstract (Originalsprache)
Fire accidents due to oil-immersed transformers seriously threaten the safe operation of power systems. In this paper, the similarity principle was used to design a high-pressure water mist fire-extinguishing test platform for a small-scale transformer fire, and the design method achieved a good fire extinguishing effect. The results indicate that a deflagration phenomenon, lasting about 2–4 s, could be observed after activating the high-pressure water mist system; the flame temperature rose rapidly at first, then dropped sharply, and finally cooled to the indoor temperature. The nozzle’s flow rate in this system has a significant impact on the fire extinguishing time. Meanwhile, the adjustment of the upper nozzle height also influenced the fire suppression effectiveness of the system, where a height of 1800 mm achieved the best performance compared to the others. In addition, the ambient wind speed is a very unfavorable factor for transformer fire suppression, where the fire extinguishing efficiency decreases rapidly with the increase in wind speed. Therefore, under low wind speed conditions, the high-pressure water mist system has great advantages in the fire suppression of outdoor oil-immersed transformers, and the above research results can provide a reference for the optimization design of this system.
Förderung
- National Natural Science Foundation of China
- Henan Provincial Science and Technology Research Project
Zitieren
APA
Song, H., Yao, H., Wei, X., Qin, H., Li, Y., Lv, K., & Chen, Q. (2023). Experimental Study on Fire Suppression of the Outdoor Oil-Immersed Transformer by High-Pressure Water Mist System. Fire, 6(6), 238. https://doi.org/10.3390/fire6060238
Vancouver
Song H, Yao H, Wei X, Qin H, Li Y, Lv K, et al. Experimental Study on Fire Suppression of the Outdoor Oil-Immersed Transformer by High-Pressure Water Mist System. Fire. 2023;6(6):238. doi:10.3390/fire6060238
BibTeX
@article{Song2023,
author = {Song, Huaitao and Yao, Haowei and Wei, Xiaoge and Qin, Hengjie and Li, Youxin and Lv, Kefeng and Chen, Qianlong},
title = {Experimental Study on Fire Suppression of the Outdoor Oil-Immersed Transformer by High-Pressure Water Mist System},
journal = {Fire},
year = {2023},
volume = {6},
number = {6},
pages = {238},
doi = {10.3390/fire6060238}
}