Integrated Insulation Coordination for Pollution- and Lightning-Exposed Medium-Voltage Distribution Networks
Eng · 18.11.2026 · 7 (11) · 658
DOI: 10.3390/eng7110658 ↗Kurz gefasst
Fachartikel in der Zeitschrift Eng, online erschienen am 18.11.2026. Verfasst von Danny Cuñas und 2 weiteren Autor:innen. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0). Gefördert von: Universidad Politécnica Salesiana.
Abstract (Originalsprache)
Medium-voltage overhead distribution networks are exposed to atmospheric overvoltages and environmental pollution that can compromise external insulation performance. This paper proposes an integrated methodology for insulation coordination, surge-arrester verification, and identification of insulation design deficiencies under specified operating and environmental conditions. The methodology combines IEC 60071 and IEC 60815 requirements with electrical simulations performed in DIgSILENT PowerFactory using the IEEE 34-node distribution feeder. At Bus 832, the simulated representative electrical stresses were 18.462 kV RMS for temporary overvoltage, 35.533 kV peak for slow-front overvoltage, and 63.942 kV peak for fast-front overvoltage. After applying the corresponding coordination and atmospheric correction factors, the required withstand voltages remained below the selected standardized insulation levels of 70 kV RMS and 145 kV peak, with a commercial equipment rating of 150 kV BIL considered separately. The 18 kV surge arrester, with a maximum continuous operating voltage of 15.3 kV, satisfied the evaluated electrical requirements. Its simulated residual voltage differed by 0.247% from the catalog reference value, confirming numerical consistency at the selected operating point. Under the assumed Quito reference altitude and pollution correction factors, the ANSI 56-3 insulator, with a creepage distance of 533 mm, satisfied the requirements for pollution severity class a but exhibited a 114.2 mm deficit for class b. Furthermore, the simulated phase-to-ground fault resulted in the interruption of 83.09% of the feeder’s initial active power. The main contribution is a traceable procedure that distinguishes electrical coordination compliance from environmental insulation deficiencies, enabling targeted mitigation while preserving adequately coordinated components. The identified creepage-distance deficiency is conditional on the assumed pollution severity, and reductions in flashover occurrence and reliability indices require subsequent field-data validation.
Förderung
- Universidad Politécnica Salesiana
Zitieren
APA
Cuñas, D., Carrión, D., & Jaramillo, M. (2026). Integrated Insulation Coordination for Pollution- and Lightning-Exposed Medium-Voltage Distribution Networks. Eng, 7(11), 658. https://doi.org/10.3390/eng7110658
Vancouver
Cuñas D, Carrión D, Jaramillo M. Integrated Insulation Coordination for Pollution- and Lightning-Exposed Medium-Voltage Distribution Networks. Eng. 2026;7(11):658. doi:10.3390/eng7110658
BibTeX
@article{Cuas2026,
author = {Cuñas, Danny and Carrión, Diego and Jaramillo, Manuel},
title = {Integrated Insulation Coordination for Pollution- and Lightning-Exposed Medium-Voltage Distribution Networks},
journal = {Eng},
year = {2026},
volume = {7},
number = {11},
pages = {658},
doi = {10.3390/eng7110658}
}
EUVIMED