Substation Operational State Assessment and Short-Term Prediction Based on Micro-Phasor Measurement Unit Data
Energies · 20.11.2026 · 19 (22) · 5614
DOI: 10.3390/en19225614 ↗Kurz gefasst
Fachartikel in der Zeitschrift Energies, online erschienen am 20.11.2026. Verfasst von Peng Li und 2 weiteren Autor:innen. Die Arbeit nennt 25 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0). Gefördert von: Ministry of Small and Medium-sized Enterprises (SMEs) and Startups.
Abstract (Originalsprache)
This study developed a field-measurement framework for substation operating-state assessment and next-day prediction using 32 micro-phasor measurement units (μPMUs) at Yeonggwang Substation, Republic of Korea. Positive-sequence voltage deviation, voltage unbalance factor, frequency deviation, and normalized one-minute positive-sequence voltage range were used to calculate the Health Index (HI) and Running State Index (RSI). The daily RSI combined the full-day mean with the mean of the lowest 5% of valid minute scores. The 21-day record yielded 480 development and 160 held-out μPMU-day pairs. Four-fold expanding-window validation selected Ridge regression with F4 inputs (α = 100; MAE = 0.4672). On the independent test set, Historical Mean achieved lower μPMU-level and station-level MAEs (0.2993 and 0.1809 RSI points) than Ridge (0.3918 and 0.2105). In nine development-period sensitivity scenarios, changes in feature weights, scoring anchors, the voltage-range definition, and daily aggregation affected the resulting RSI; HI equaled 100 in 96.25% of valid minutes. All four models predicted scores above the cutoff for each of the 11 test cases with RSI at or below P10. The findings demonstrate an auditable measurement-to-assessment pipeline and the importance of simple baselines, while the short test period, upper-score saturation, and low-score misses limit operational deployment claims.
Förderung
- Ministry of Small and Medium-sized Enterprises (SMEs) and Startups
Zitieren
APA
Li, P., Lee, K., & Choi, Y. (2026). Substation Operational State Assessment and Short-Term Prediction Based on Micro-Phasor Measurement Unit Data. Energies, 19(22), 5614. https://doi.org/10.3390/en19225614
Vancouver
Li P, Lee K, Choi Y. Substation Operational State Assessment and Short-Term Prediction Based on Micro-Phasor Measurement Unit Data. Energies. 2026;19(22):5614. doi:10.3390/en19225614
BibTeX
@article{Li2026,
author = {Li, Peng and Lee, Kyung-Min and Choi, Yong-Sung},
title = {Substation Operational State Assessment and Short-Term Prediction Based on Micro-Phasor Measurement Unit Data},
journal = {Energies},
year = {2026},
volume = {19},
number = {22},
pages = {5614},
doi = {10.3390/en19225614}
}