Electrothermal Failure Mechanism of Multi-Finger Contacts in a Disconnector Under Foundation-Induced Displacement
Energies · 17.11.2026 · 19 (22) · 5563
DOI: 10.3390/en19225563 ↗Kurz gefasst
Fachartikel in der Zeitschrift Energies, online erschienen am 17.11.2026. Verfasst von Jia Zhang und 6 weiteren Autor:innen. Die Arbeit nennt 30 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0). Gefördert von: Science and Technology Project of State Grid Gansu Electric Power Company.
Abstract (Originalsprache)
To clarify the electrothermal failure of fixed contacts in a 363 kV three-phase five-column disconnector, field inspection, circuit-resistance tests, contact-mechanical modeling, finger-level resistance calculation, and electrothermal simulation were combined. The fault side had approximately 10 mm settlement and 51 mm horizontal displacement. Unserved contacts remained at 81–83 μΩ, whereas field-served contacts showed displacement-sensitive, non-monotonic resistance changes. A finite element model of 24 contact fingers with assembly-induced prestress was developed. Contact pressures were calculated under normal, settlement, and combined settlement—horizontal displacement conditions. Normal force was integrated over each contact area, and zero pressure denoted contact loss. The force, contact length, and equivalent contact width were used in a cylinder-on-flat model to calculate finger resistance. These resistances were connected in parallel and calibrated against the measured normal-state resistance of 83.57 μΩ. Settlement redistributed load from lower to upper fingers, while further horizontal displacement concentrated contact on one side; eastward displacement caused all bottom-row fingers to lose contact. Electrothermal simulation showed little temperature change while most fingers remained in contact, but temperatures exceeded 130 °C after bottom-row contact loss. Thus, total resistance can conceal local degradation, while load redistribution and current concentration increase Joule heating in remaining paths and explain burnout.
Förderung
- Science and Technology Project of State Grid Gansu Electric Power Company
Zitieren
APA
Zhang, J., Chen, B., Liu, K., Wu, T., Wang, H., Wang, L., & Wen, M. (2026). Electrothermal Failure Mechanism of Multi-Finger Contacts in a Disconnector Under Foundation-Induced Displacement. Energies, 19(22), 5563. https://doi.org/10.3390/en19225563
Vancouver
Zhang J, Chen B, Liu K, Wu T, Wang H, Wang L, et al. Electrothermal Failure Mechanism of Multi-Finger Contacts in a Disconnector Under Foundation-Induced Displacement. Energies. 2026;19(22):5563. doi:10.3390/en19225563
BibTeX
@article{Zhang2026,
author = {Zhang, Jia and Chen, Bodong and Liu, Kang and Wu, Tiancun and Wang, Hailong and Wang, Luyao and Wen, Miao},
title = {Electrothermal Failure Mechanism of Multi-Finger Contacts in a Disconnector Under Foundation-Induced Displacement},
journal = {Energies},
year = {2026},
volume = {19},
number = {22},
pages = {5563},
doi = {10.3390/en19225563}
}