EUVIMEDEUVIMED entdecken
Open Access · CC BY 4.0

Topology-Aware Feasibility Assessment and Coordinated Setting of Transformer Primary and Backup Protection in Islanded Renewable Power Systems

Qi Zhu, Yu Sun, Lie Li, Yifan Zhao

Energies · 13.11.2026 · 19 (22) · 5473

DOI: 10.3390/en19225473 ↗

Kurz gefasst

Fachartikel in der Zeitschrift Energies, online erschienen am 13.11.2026. Verfasst von Qi Zhu und 3 weiteren Autor:innen. Die Arbeit nennt 45 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0). Gefördert von: State Grid Hubei Electric Power Company Ltd..

AbstractBibliografische AngabenZitierenVerwandte Studien

Abstract (Originalsprache)

Islanded microgrid topology and converter current limiting can alter transformer protection currents. We formulate primary and backup coordination as a topology-indexed feasible domain. A bridge test identifies source contributions that cross the protected transformer, and a joint model tests differential sensitivity and stability, overcurrent pickup and timing, load security, and device limits. At the selected inputs, four supported bridge states in an eight-entry reference library retain non-empty domains. The weak-GFL case has a narrow backup–pickup interval (0.984–1.042 pu), and its feasibility classification changes across the tested lower-current factors; the high-load case remains empty (1.860 pu load-security lower bound versus 1.326 pu sensitivity upper bound). A seven-bus reference EMT study includes 112 baseline cases, a 1232-case direction/location/resistance scan, and a 288-case coupled-controller scan. The CT stress screen reduces the all-source reference-domain volume from 0.08391 to 0.07059. All numerical results use the declared reference-network and device inputs.

Förderung

  • State Grid Hubei Electric Power Company Ltd.

Zitieren

APA

Zhu, Q., Sun, Y., Li, L., & Zhao, Y. (2026). Topology-Aware Feasibility Assessment and Coordinated Setting of Transformer Primary and Backup Protection in Islanded Renewable Power Systems. Energies, 19(22), 5473. https://doi.org/10.3390/en19225473

Vancouver

Zhu Q, Sun Y, Li L, Zhao Y. Topology-Aware Feasibility Assessment and Coordinated Setting of Transformer Primary and Backup Protection in Islanded Renewable Power Systems. Energies. 2026;19(22):5473. doi:10.3390/en19225473

BibTeX
@article{Zhu2026,
  author = {Zhu, Qi and Sun, Yu and Li, Lie and Zhao, Yifan},
  title = {Topology-Aware Feasibility Assessment and Coordinated Setting of Transformer Primary and Backup Protection in Islanded Renewable Power Systems},
  journal = {Energies},
  year = {2026},
  volume = {19},
  number = {22},
  pages = {5473},
  doi = {10.3390/en19225473}
}
Kostenlos starten →