A Non-Pilot Accelerated Distance Protection Scheme Based on RCBO for SLG Faults on IBR-Connected Transmission Lines
Energies · 09.11.2026 · 19 (21) · 5375
DOI: 10.3390/en19215375 ↗Kurz gefasst
Fachartikel in der Zeitschrift Energies, online erschienen am 09.11.2026. Verfasst von Xiaokai Wang und 3 weiteren Autor:innen. Die Arbeit nennt 31 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0). Gefördert von: Major Program of Smart Grid 2030.
Abstract (Originalsprache)
High-resistance single-line-to-ground (SLG) faults on inverter-based resource (IBR)-connected transmission lines can cause severe underreach of distance protection because the limited and control-dependent IBR fault current increases the influence of fault resistance on the measured apparent impedance. Consequently, the local Zone-II element may fail to pick up, preventing conventional pickup-dependent acceleration from being initiated. This paper proposes a non-pilot accelerated distance protection scheme for SLG faults that requires neither interstation communication nor local Zone-II pickup. Following remote single-pole opening, the fault-sequence current is reconstructed from the open-pole condition using a segmented nominal-π line model that accounts for line charging. Combining the negative- and zero-sequence boundary equations yields a fault-location residual without an explicit fault-resistance term. The required remote-system source impedance is updated from locally stored prefault phasors, subject to numerical and physical validity checks. Candidate open-pole residuals, a fault-location stability criterion, and a boundary safety margin supervise the acceleration decision. Across 540 PSCAD/EMTDC fault scenarios covering six system configurations, the maximum fault-location error was 1.98%; all 270 tested internal faults within the prescribed acceleration range were successfully accelerated, and all 270 external faults were correctly blocked. The mean post-RCBO trip-decision times ranged from 37 to 45 ms across the six configurations.
Förderung
- Major Program of Smart Grid 2030
Zitieren
APA
Wang, X., He, A., Li, S., & Xu, Q. (2026). A Non-Pilot Accelerated Distance Protection Scheme Based on RCBO for SLG Faults on IBR-Connected Transmission Lines. Energies, 19(21), 5375. https://doi.org/10.3390/en19215375
Vancouver
Wang X, He A, Li S, Xu Q. A Non-Pilot Accelerated Distance Protection Scheme Based on RCBO for SLG Faults on IBR-Connected Transmission Lines. Energies. 2026;19(21):5375. doi:10.3390/en19215375
BibTeX
@article{Wang2026,
author = {Wang, Xiaokai and He, Anqi and Li, Shangwen and Xu, Qian},
title = {A Non-Pilot Accelerated Distance Protection Scheme Based on RCBO for SLG Faults on IBR-Connected Transmission Lines},
journal = {Energies},
year = {2026},
volume = {19},
number = {21},
pages = {5375},
doi = {10.3390/en19215375}
}