EUVIMEDEUVIMED entdecken
Open Access · CC BY 4.0

Architectural Vulnerability Mapping and Analysis in Hybrid AC/DC Distribution Networks

Krishna Kumar, Ramesh Rayudu, Aleksandra Lekić, Tek Tjing Lie, Nirmal-Kumar C. Nair

Energies · 07.11.2026 · 19 (21) · 5357

DOI: 10.3390/en19215357 ↗

Kurz gefasst

Fachartikel in der Zeitschrift Energies, online erschienen am 07.11.2026. Verfasst von Krishna Kumar und 4 weiteren Autor:innen. Die Arbeit nennt 72 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0). Gefördert von: New Zealand Ministry of Business, Innovation, and Employment.

AbstractBibliografische AngabenZitierenVerwandte Studien

Abstract (Originalsprache)

The growing integration of distributed renewable resources is pushing medium-voltage distribution grids toward hybrid AC/DC configurations, whose topology-dependent vulnerabilities, including harmonic resonance, sub-synchronous & converter-control interactions (SSCI/CCI), AC/DC interface faults, and protection miscoordination, remain poorly addressed. This paper develops a vulnerability mapping framework for hybrid MVAC/MVDC systems that combines multilayer network topology modelling, multi-source harmonic-domain analysis using frequency coupling matrices, and Backward-Forward Sweep power flow. The relationship between topology, resonant-mode count, and SSCI phase-margin coupling is derived analytically from the admittance matrix. The framework is applied to 12 configurations across four topologies, using phasor-domain simulation with electromagnetic transient (EMT) verification of fault and converter cases. The results show that, for an XLPE 95 mm2 DC cable, the dominant resonance falls below 200 Hz for feeders longer than about 12.6 km; Monte Carlo analysis places this crossing at 10.0–14.2 km (5th–95th percentile). At 60% renewable penetration, four configurations (C5, C8, C9, C12) exceed the unity resonance-vulnerability threshold, and the meshed DC-side grid-forming configuration (C8) violates the 30° phase-margin limit. Because the penetration at which this limit is lost ranges from 20% to 85%, grid-forming deployment should rely on configuration-specific impedance and phase-margin assessment rather than a universal threshold. Overcurrent relays misoperate in 31–61% of DC pole-to-ground faults, reflecting a mismatch between magnitude-based protection and DC fault signatures under high-impedance grounding. A long short-term memory (LSTM) classifier trained on 468 simulated scenarios achieves 94.4% accuracy on 120 held-out scenarios under noise-free conditions, but its RVI, SVI, and FPSS accuracy fall to 42.5–50.8% when the meshed topology class is withheld, so each topology class must be represented in the training data.

Förderung

  • New Zealand Ministry of Business, Innovation, and Employment

Zitieren

APA

Kumar, K., Rayudu, R., Lekić, A., Lie, T. T., & Nair, N. C. (2026). Architectural Vulnerability Mapping and Analysis in Hybrid AC/DC Distribution Networks. Energies, 19(21), 5357. https://doi.org/10.3390/en19215357

Vancouver

Kumar K, Rayudu R, Lekić A, Lie TT, Nair NC. Architectural Vulnerability Mapping and Analysis in Hybrid AC/DC Distribution Networks. Energies. 2026;19(21):5357. doi:10.3390/en19215357

BibTeX
@article{Kumar2026,
  author = {Kumar, Krishna and Rayudu, Ramesh and Lekić, Aleksandra and Lie, Tek Tjing and Nair, Nirmal-Kumar C.},
  title = {Architectural Vulnerability Mapping and Analysis in Hybrid AC/DC Distribution Networks},
  journal = {Energies},
  year = {2026},
  volume = {19},
  number = {21},
  pages = {5357},
  doi = {10.3390/en19215357}
}