Short-Term Load Forecasting for Secondary Substations in Electrical Distribution Networks

Diego Andreotti, Matteo Spiller, Giuliano Rancilio, Marco Merlo

Energies · 07.11.2026 · 19 (21) · 5356

DOI: 10.3390/en19215356 ↗

Kurz gefasst

Fachartikel in der Zeitschrift Energies, online erschienen am 07.11.2026. Verfasst von Diego Andreotti und 3 weiteren Autor:innen. Die Arbeit nennt 28 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0). Gefördert von: Italian Ministry of Environment and Energy Security.

AbstractBibliografische AngabenZitierenVerwandte Studien

Abstract (Originalsprache)

The increasing penetration of distributed energy resources (DERs) and new electric loads associated with decarbonization is pushing Distribution System Operators (DSOs) towards more proactive management of Medium Voltage (MV) and Low Voltage (LV) networks. In this context, short-term load forecasting (STLF) at the secondary substation (SS) level is becoming increasingly relevant for network operation and planning. However, conventional approaches typically use exclusively the data at the SS level, without exploiting information available across the distribution network. This paper proposes a data-driven hierarchical forecasting framework that combines substation-level predictions with aggregated forecasts of the underlying connection points. SS are characterized according to their operating conditions, based on the balance between annually consumed and produced energy, to investigate how these affect predictability. Forecasts from one to five days ahead are obtained using horizon-specific Random Forest (RF) models combining autoregressive, meteorological, and calendar information. Minimum Trace (MinT) reconciliation then ensures coherence between substation-level and connection-point forecasts. The analysis reveals markedly different forecasting behavior across operating conditions, with consumption-dominated substations proving considerably more predictable than their generation-dominated counterparts, as reflected in median day-ahead weighted absolute percentage errors of 9.2% and 79%, respectively. Hierarchical reconciliation follows the same pattern, delivering its most consistent gains for passive substations, with a median day-ahead MAE reduction of 2.8%, reaching up to 4.6%, while its benefit gradually fades as local generation grows. The results provide DSOs with practical indications for adapting forecasting and reconciliation strategies across heterogeneous distribution networks.

Förderung

  • Italian Ministry of Environment and Energy Security

Zitieren

APA

Andreotti, D., Spiller, M., Rancilio, G., & Merlo, M. (2026). Short-Term Load Forecasting for Secondary Substations in Electrical Distribution Networks. Energies, 19(21), 5356. https://doi.org/10.3390/en19215356

Vancouver

Andreotti D, Spiller M, Rancilio G, Merlo M. Short-Term Load Forecasting for Secondary Substations in Electrical Distribution Networks. Energies. 2026;19(21):5356. doi:10.3390/en19215356

BibTeX
@article{Andreotti2026,
  author = {Andreotti, Diego and Spiller, Matteo and Rancilio, Giuliano and Merlo, Marco},
  title = {Short-Term Load Forecasting for Secondary Substations in Electrical Distribution Networks},
  journal = {Energies},
  year = {2026},
  volume = {19},
  number = {21},
  pages = {5356},