Control-Aware Multi-Horizon PUE Forecasting for Coordinated Data Center Demand-Side Management and Microgrid Dispatch
Energies · 16.08.2026 · 19 (16) · 3840
DOI: 10.3390/en19163840 ↗Kurz gefasst
Fachartikel in der Zeitschrift Energies, online erschienen am 16.08.2026. Verfasst von Yingqi Liang und 3 weiteren Autor:innen. Die Arbeit wurde bisher 1-mal zitiert (Crossref) und nennt 28 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0). Gefördert von: National Key Research and Development Program of China, Ministry of Science and Technology of the People’s Republic of China.
Abstract (Originalsprache)
Data centers can provide demand-side flexibility by coordinating computing workloads, cooling systems, and on-site energy resources. However, facility demand varies with information technology (IT) load and cooling operation, making a fixed power usage effectiveness (PUE) or a forecast independent of planned controls inconsistent with dispatch. This paper proposes a control-aware, multi-horizon PUE forecasting framework for coordinated data center demand-side management (DSM) and microgrid dispatch. The key idea of this control-aware approach is to forecast PUE using planned workload and cooling schedules as inputs. A power-consistent Temporal Fusion Transformer (PC-TFT) predicts quantiles of non-IT overhead power and rack inlet temperature from telemetry, weather forecasts, admitted requests, and candidate workload and cooling schedules. Facility power and PUE are derived from the algebraic power balance, ensuring consistency among IT, overhead, and facility power and PUE values no lower than 1. Empirical split conformal calibration and temporally dependent scenarios characterize forecast uncertainty. A trajectory-conditioned piecewise-affine control response map with a recursive thermal state links the forecasts to a risk-informed model predictive controller that coordinates workloads, cooling, photovoltaic generation, battery storage, and grid exchange. The proposed framework is validated through EnergyPlus simulations of a Shenzhen data center, coupled with workload and microgrid simulations. Forecasting performance is compared with persistence and matched-input neural baselines, while dispatch is benchmarked against deterministic and oracle controllers. The results demonstrate improved multi-horizon PUE forecasting accuracy and empirical interval calibration, lower operating cost and peak grid demand, higher renewable energy utilization, and fewer service quality violations. These findings indicate that control-aware, power-balance-constrained probabilistic PUE forecasts can provide a reliable basis for coordinated data center DSM and microgrid dispatch.
Förderung
- National Key Research and Development Program of China, Ministry of Science and Technology of the People’s Republic of China
Zitieren
APA
Liang, Y., Peng, J., Fu, G., & Srinivasan, D. (2026). Control-Aware Multi-Horizon PUE Forecasting for Coordinated Data Center Demand-Side Management and Microgrid Dispatch. Energies, 19(16), 3840. https://doi.org/10.3390/en19163840
Vancouver
Liang Y, Peng J, Fu G, Srinivasan D. Control-Aware Multi-Horizon PUE Forecasting for Coordinated Data Center Demand-Side Management and Microgrid Dispatch. Energies. 2026;19(16):3840. doi:10.3390/en19163840
BibTeX
@article{Liang2026,
author = {Liang, Yingqi and Peng, Junjie and Fu, Guanyu and Srinivasan, Dipti},
title = {Control-Aware Multi-Horizon PUE Forecasting for Coordinated Data Center Demand-Side Management and Microgrid Dispatch},
journal = {Energies},
year = {2026},
volume = {19},
number = {16},
pages = {3840},
doi = {10.3390/en19163840}
}