Abstract (Originalsprache)

Traveling-wave fault location in distribution networks confronts two fundamental challenges: insufficient robustness of the cost function against heavy-tailed synchronization noise, and the location-resolution bottleneck imposed by the discrete search step. Starting from first physical principles, we identify that faulty-branch identity is encoded in the ordering pattern of multi-terminal TW arrival times rather than in their absolute values. Building on this insight, we propose a faulty-branch identification and precise fault-location method that integrates amplitude-assisted rank correlation (AAC) features with random forest (RF). At the theoretical level, we employ Hampel’s finite-sample breakdown-point framework to quantitatively establish that the L2 cost function has an asymptotic breakdown point of zero, whereas the Spearman rank correlation coefficient attains an asymptotic breakdown point of 0.5—providing a rigorous robustness justification for replacing the L2 residual with a rank-consistency cost. At the algorithmic level, the method consists of a three-stage inference pipeline: AAC computes a joint rank correlation cost for every line section across the network and extracts a 42-dimensional feature vector encompassing cost statistics, timing residuals, and topological attributes; feature selection is performed via fused ranking, which combines Pearson correlation, point-biserial correlation, and RF out-of-bag permutation importance through a weighted harmonic mean; the RF classifier directly performs branch identification over the full edge space, and the RF regressor predicts the coarse-location residual from local cost-terrain statistical features along the correctly identified branch, breaking through the 20 m search-step resolution bottleneck. We construct a five-layer physical noise model covering wavefront detection, time synchronization, wave-velocity deviation, reflected-wave misdetection, and terminal failure. Experiments on three structurally distinct 10 kV radial distribution network topologies, each with 5000 independently generated fault samples, demonstrate that branch identification accuracy remains stably above 94%, and residual correction reduces the mean location error from approximately 60 m to approximately 40 m—an improvement exceeding 30%—confirming the effectiveness of the physics–data hybrid framework for TW fault location in distribution networks.

Zitieren

APA

Yu, Y., Hou, S., Sang, Y., & Xue, Q. (2026). Traveling-Wave Fault Location in Distribution Networks Based on Rank-Correlation and Random Forest. Energies, 19(16), 3782. https://doi.org/10.3390/en19163782

Vancouver

Yu Y, Hou S, Sang Y, Xue Q. Traveling-Wave Fault Location in Distribution Networks Based on Rank-Correlation and Random Forest. Energies. 2026;19(16):3782. doi:10.3390/en19163782

BibTeX
@article{Yu2026,
  author = {Yu, Yifan and Hou, Sizu and Sang, Yao and Xue, Qiwei},
  title = {Traveling-Wave Fault Location in Distribution Networks Based on Rank-Correlation and Random Forest},
  journal = {Energies},
  year = {2026},
  volume = {19},
  number = {16},
  pages = {3782},
  doi = {10.3390/en19163782}
}
Kostenlos starten →