T-HMM-Based Transformer Fault Diagnosis in Grid-Connected Renewable Energy Systems
Energies · 06.08.2026 · 19 (15) · 3694
DOI: 10.3390/en19153694 ↗Kurz gefasst
Fachartikel in der Zeitschrift Energies, online erschienen am 06.08.2026. Verfasst von Wei Li und 12 weiteren Autor:innen. Die Arbeit nennt 34 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0). Gefördert von: Research on a Portable Grounding Network Impedance Measurement Device with Distributed Current Phasor Measurement Function.
Abstract (Originalsprache)
Addressing multi-factor coupling, progressive degradation, and time-varying operating conditions in substation equipment under high-penetration renewable energy integration, this paper proposes a Time-varying Hidden Markov Model (T-HMM) for transformer fault diagnosis using multi-source heterogeneous data. Unlike conventional HMM with fixed transition matrices and initial parameter sensitivity, the proposed framework introduces a forgetting-factor-driven online transition matrix updating mechanism, enabling adaptive state tracking under varying operating conditions. A multi-dimensional feature system is constructed incorporating fundamental state, coupling correlation, and temporal evolution characteristics, with state-dependent sliding window standardization and adaptive wavelet denoising to enhance early-stage fault discriminability. Parameter optimization employs pre-clustering and multi-start strategies to circumvent local optima in the Baum–Welch algorithm, while an improved decoding strategy achieves real-time health state identification and multi-step probability prediction. Experimental results demonstrate that the proposed method accurately tracks state evolution trends and effectively identifies fault categories, achieving significantly superior state recognition accuracy and multi-step prediction hit rates compared to conventional HMM, with substantially reduced mean absolute error. The method effectively captures subtle precursors during normal-to-fault transitions, providing reliable theoretical foundations for early fault warning and condition-based maintenance.
Förderung
- Research on a Portable Grounding Network Impedance Measurement Device with Distributed Current Phasor Measurement Function
Zitieren
APA
Li, W., Gu, S., Shen, L., Wang, C., Shi, Y., Zhu, G., Zhuang, F., Wang, J., Liu, C., Ding, Z., Xia, X., Liu, B., & Ji, J. (2026). T-HMM-Based Transformer Fault Diagnosis in Grid-Connected Renewable Energy Systems. Energies, 19(15), 3694. https://doi.org/10.3390/en19153694
Vancouver
Li W, Gu S, Shen L, Wang C, Shi Y, Zhu G, et al. T-HMM-Based Transformer Fault Diagnosis in Grid-Connected Renewable Energy Systems. Energies. 2026;19(15):3694. doi:10.3390/en19153694
BibTeX
@article{Li2026,
author = {Li, Wei and Gu, Shanyun and Shen, Lei and Wang, Chen and Shi, Yongkun and Zhu, Guanjian and Zhuang, Fei and Wang, Jiaqiang and Liu, Chao and Ding, Zujun and Xia, Xin and Liu, Baolian and Ji, Jie},
title = {T-HMM-Based Transformer Fault Diagnosis in Grid-Connected Renewable Energy Systems},
journal = {Energies},
year = {2026},
volume = {19},
number = {15},
pages = {3694},
doi = {10.3390/en19153694}
}