Fault Section Location Based on Transient Zero-Sequence Current Waveform Dissimilarity for Single-Phase Grounding Faults in Distribution Networks
Energies · 04.08.2026 · 19 (15) · 3654
DOI: 10.3390/en19153654 ↗Kurz gefasst
Fachartikel in der Zeitschrift Energies, online erschienen am 04.08.2026. Verfasst von Yuxing Lei und 5 weiteren Autor:innen. Die Arbeit nennt 22 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0). Gefördert von: Science and Technology Project of China Southern Power Grid Co., Ltd.
Abstract (Originalsprache)
A fault-section location method based on waveform-difference analysis of transient zero-sequence currents is proposed for distribution networks with small-current grounding systems. The method addresses weak single-phase-to-ground fault-current amplitudes, indistinct fault features, and limited adaptability of steady-state-quantity-based location criteria under arc-suppression-coil compensation. Steady-state and transient characteristics of single-phase-to-ground faults were analyzed in neutral-point ungrounded systems and arc-suppression-coil-grounded systems. Transient zero-sequence currents exhibited more pronounced amplitude, polarity, and waveform differences than steady-state zero-sequence currents, with lower sensitivity to compensation effects. These characteristics provide effective features for fault-section discrimination. The discrete Fréchet distance was used to quantify the overall waveform difference between transient zero-sequence currents at both ends of each line section. The coefficient of variation was introduced to characterize the dispersion of waveform differences among different sections. A fault-section location criterion was then constructed. The location performance was verified through PSCAD/EMTDC–MATLAB co-simulation under different neutral-point grounding modes, transition resistances, and fault inception angles. The results show that the proposed method accurately identifies fault sections and maintains good adaptability under both distinct and weak fault-feature conditions. Compared with the correlation-coefficient method, grey relational analysis, and empirical mode decomposition, the proposed method more comprehensively characterizes waveform differences in transient zero-sequence currents at both ends of a line section. It shows good section-discrimination capability under the representative fault conditions considered in this study.
Förderung
- Science and Technology Project of China Southern Power Grid Co., Ltd
Zitieren
APA
Lei, Y., Li, B., Yin, Y., Wei, L., Sun, J., & Wu, Z. (2026). Fault Section Location Based on Transient Zero-Sequence Current Waveform Dissimilarity for Single-Phase Grounding Faults in Distribution Networks. Energies, 19(15), 3654. https://doi.org/10.3390/en19153654
Vancouver
Lei Y, Li B, Yin Y, Wei L, Sun J, Wu Z. Fault Section Location Based on Transient Zero-Sequence Current Waveform Dissimilarity for Single-Phase Grounding Faults in Distribution Networks. Energies. 2026;19(15):3654. doi:10.3390/en19153654
BibTeX
@article{Lei2026,
author = {Lei, Yuxing and Li, Bo and Yin, Yingjie and Wei, Ling and Sun, Jiao and Wu, Zhensheng},
title = {Fault Section Location Based on Transient Zero-Sequence Current Waveform Dissimilarity for Single-Phase Grounding Faults in Distribution Networks},
journal = {Energies},
year = {2026},
volume = {19},
number = {15},
pages = {3654},
doi = {10.3390/en19153654}
}
EUVIMED