High-Frequency Oscillation Suppression Strategy for Interconnected Grid-Forming Energy Storage and Grid-Following HVDC Systems Based on Impedance Analysis
Energies · 03.08.2026 · 19 (15) · 3635
DOI: 10.3390/en19153635 ↗Kurz gefasst
Fachartikel in der Zeitschrift Energies, online erschienen am 03.08.2026. Verfasst von Jun Deng und 3 weiteren Autor:innen. Die Arbeit nennt 23 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0). Gefördert von: State Grid Shaanxi Electric Power Company Limited.
Abstract (Originalsprache)
Interconnecting grid-following (GFL) and grid-forming (GFM) converters help stabilize weak grids with a high penetration of power electronics, but dynamic interactions can induce high-frequency oscillations (HFOs). The HFO mechanism within interconnected grid-forming battery energy storage (GFM-BESS) and grid-following VSC-HVDC systems remains unresolved, with viable suppression strategies yet to be established. To address this, this study utilizes harmonic linearization to derive small-signal frequency-domain impedance models for both devices. The models are developed for high-frequency-oscillation analysis: the GFM-BESS model retains all control loops, while the GFL-HVDC model retains the current loop and the phase-locked loop, with the slow outer loop omitted as justified within the high-frequency band. Frequency-coupled 2×2 impedance matrices are established to capture the frequency coupling introduced by the power loops and the phase-locked loop. Stability is established by the argument principle, the exact Nyquist encirclement count and the roots of the closed-loop characteristic function. At a nominal control delay of 50 μs, the voltage-loop proportional gain has two finite stability boundaries: insufficient proportional action fails to damp the integral-loop mode, whereas excessive proportional action destabilizes the delay-affected filter mode. The resulting two-sided admissible interval is 0.0771
Förderung
- State Grid Shaanxi Electric Power Company Limited
Zitieren
APA
Deng, J., Wang, X., Wang, Y., & Wang, W. (2026). High-Frequency Oscillation Suppression Strategy for Interconnected Grid-Forming Energy Storage and Grid-Following HVDC Systems Based on Impedance Analysis. Energies, 19(15), 3635. https://doi.org/10.3390/en19153635
Vancouver
Deng J, Wang X, Wang Y, Wang W. High-Frequency Oscillation Suppression Strategy for Interconnected Grid-Forming Energy Storage and Grid-Following HVDC Systems Based on Impedance Analysis. Energies. 2026;19(15):3635. doi:10.3390/en19153635
BibTeX
@article{Deng2026,
author = {Deng, Jun and Wang, Xiaoping and Wang, Yichun and Wang, Weixiang},
title = {High-Frequency Oscillation Suppression Strategy for Interconnected Grid-Forming Energy Storage and Grid-Following HVDC Systems Based on Impedance Analysis},
journal = {Energies},
year = {2026},
volume = {19},
number = {15},
pages = {3635},
doi = {10.3390/en19153635}
}