EUVIMEDEUVIMED entdecken
Open Access · CC BY 4.0

Local Electric-Field Direction Measurement in SF6 Based on Electric Field-Induced Second-Harmonic Generation

Junping Zhao, Chong Guo, Ming Yin, Chenyan Han, Zhengjie An, Dongliang Liu, Xiao’ang Li, Yuyi Wu

Energies · 28.07.2026 · 19 (15) · 3548

DOI: 10.3390/en19153548 ↗

Kurz gefasst

Fachartikel in der Zeitschrift Energies, online erschienen am 28.07.2026. Verfasst von Junping Zhao und 7 weiteren Autor:innen. Die Arbeit nennt 30 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0). Gefördert von: State Grid Corporation of China.

AbstractBibliografische AngabenZitierenVerwandte Studien

Abstract (Originalsprache)

Non-intrusive measurement of the local electric-field direction in SF6 gas-insulated equipment is important for insulation-condition assessment and electric-field distortion analysis. In this study, a three-projection electric-field direction measurement method based on electric field-induced second-harmonic generation is proposed. The feasibility of the method is validated using a known reference electric field, and the effects of electric-field strength, laser pulse energy, SF6 pressure, and spatial electric-field non-uniformity on the direction-retrieval results are systematically investigated. The results show that increasing the electric-field strength or laser pulse energy enhances the second-harmonic modulation signal and thus reduces the direction-retrieval deviation. SF6 pressure has a non-monotonic influence on the effective accumulation of the second-harmonic signal and the direction-retrieval accuracy through the competition between increased molecular number density and enhanced phase mismatch. Spatial electric-field non-uniformity weakens the ability of the three-projection retrieved direction to represent the local electric-field direction at the focus. Under the present experimental conditions, the maximum absolute angular deviations in the strongly non-uniform edge regions of the cylindrical and hemispherical electrodes are 6.68 ± 1.62° and 9.20 ± 1.84°, respectively.

Förderung

  • State Grid Corporation of China

Zitieren

APA

Zhao, J., Guo, C., Yin, M., Han, C., An, Z., Liu, D., Li, X., & Wu, Y. (2026). Local Electric-Field Direction Measurement in SF6 Based on Electric Field-Induced Second-Harmonic Generation. Energies, 19(15), 3548. https://doi.org/10.3390/en19153548

Vancouver

Zhao J, Guo C, Yin M, Han C, An Z, Liu D, et al. Local Electric-Field Direction Measurement in SF6 Based on Electric Field-Induced Second-Harmonic Generation. Energies. 2026;19(15):3548. doi:10.3390/en19153548

BibTeX
@article{Zhao2026,
  author = {Zhao, Junping and Guo, Chong and Yin, Ming and Han, Chenyan and An, Zhengjie and Liu, Dongliang and Li, Xiao’ang and Wu, Yuyi},
  title = {Local Electric-Field Direction Measurement in SF6 Based on Electric Field-Induced Second-Harmonic Generation},
  journal = {Energies},
  year = {2026},
  volume = {19},
  number = {15},
  pages = {3548},
  doi = {10.3390/en19153548}
}
Kostenlos starten →