Capability-Curve-Constrained Optimal Reactive Power Flow for Renewable-Integrated Transmission Systems

José Oscullo Lala, Nathaly Orozco Garzón, Henry Carvajal Mora, José Vega-Sánchez, Takaaki Ohishi

Energies · 27.07.2026 · 19 (15) · 3537

DOI: 10.3390/en19153537 ↗

Kurz gefasst

Fachartikel in der Zeitschrift Energies, online erschienen am 27.07.2026. Verfasst von José Oscullo Lala und 4 weiteren Autor:innen. Die Arbeit nennt 30 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0). Gefördert von: Universidad de Las Américas (UDLA), Quito, Ecuador, Universidad San Francisco de Quito.

AbstractBibliografische AngabenZitierenVerwandte Studien

Abstract (Originalsprache)

Optimal reactive power flow (ORPF) is a steady-state optimization problem used to determine reactive-power-related control settings in AC power systems while satisfying network operating constraints. In renewable-integrated transmission systems, explicitly representing the feasible reactive-power contribution of inverter-interfaced resources is essential, because wind, photovoltaic (PV), and battery energy storage system (BESS) units cannot operate as unlimited or overly flexible reactive-power sources. Their reactive capability depends on active-power output, apparent-power rating, voltage conditions, and equipment-level capability curves. This paper evaluates the impact of including these capability curves in the solution of the ORPF problem. A MATLAB-DIgSILENT PowerFactory co-simulation framework is implemented, in which MATLAB applies a hybrid particle swarm optimization-pattern search procedure and DIgSILENT PowerFactory performs repeated AC power-flow evaluations using detailed network models and predefined capability limits. The framework is tested on modified IEEE 39-bus and IEEE 118-bus systems with wind, PV, and BESS resources. The results show that neglecting capability curves can produce unrealistic reactive-power allocations for inverter-based units, whereas enforcing these limits shifts the ORPF solution toward operating points consistent with the modeled equipment capability. The study demonstrates the importance of capability-curve representation for obtaining physically meaningful steady-state ORPF results and supports clearer comparison of constrained and unconstrained dispatch cases.

Förderung

  • Universidad de Las Américas (UDLA), Quito, Ecuador
  • Universidad San Francisco de Quito

Zitieren

APA

Lala, J. O., Garzón, N. O., Mora, H. C., Vega-Sánchez, J., & Ohishi, T. (2026). Capability-Curve-Constrained Optimal Reactive Power Flow for Renewable-Integrated Transmission Systems. Energies, 19(15), 3537. https://doi.org/10.3390/en19153537

Vancouver

Lala JO, Garzón NO, Mora HC, Vega-Sánchez J, Ohishi T. Capability-Curve-Constrained Optimal Reactive Power Flow for Renewable-Integrated Transmission Systems. Energies. 2026;19(15):3537. doi:10.3390/en19153537

BibTeX
@article{Lala2026,
  author = {Lala, José Oscullo and Garzón, Nathaly Orozco and Mora, Henry Carvajal and Vega-Sánchez, José and Ohishi, Takaaki},
  title = {Capability-Curve-Constrained Optimal Reactive Power Flow for Renewable-Integrated Transmission Systems},
  journal = {Energies},
  year = {2026},
  volume = {19},
  number = {15},
  pages = {3537},
  doi = {10.3390/en19153537}
}
Kostenlos starten →