Topology Identification Method for Distribution Networks Based on Improved T-Type Grey Relational Analysis and Fisher Optimal Segmentation
Energies · 27.07.2026 · 19 (15) · 3524
DOI: 10.3390/en19153524 ↗Kurz gefasst
Fachartikel in der Zeitschrift Energies, online erschienen am 27.07.2026. Verfasst von Changzhi Lv und 4 weiteren Autor:innen. Die Arbeit nennt 31 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0). Gefördert von: National Natural Science Foundation of China, Key Research and Development Program of Shandong Province, Shandong Provincial Excellent Educational and Teaching Resources Program for Postgraduates.
Abstract (Originalsprache)
To address ambiguities in phase-line identification, errors in user–transformer associations, and inaccurate topology records in complex low-voltage distribution networks, this paper proposes a hierarchical topology identification method based on improved T-type grey relational analysis and Fisher optimal segmentation. In the proposed method, signed voltage increments, a resolution coefficient, and node-distance weighting are introduced to construct distance-aware relational features from user voltage sequences. Fisher optimal segmentation is subsequently applied to identify user–transformer associations, followed by a suspicious-user verification mechanism for local topology correction. Case studies using practical transformer-area data show that the proposed method provides greater discrimination among user voltage sequences than Pearson correlation analysis and conventional T-type grey relational analysis. At a random-noise level of 6%, the phase-line identification accuracy remains 83.7%, while the accuracy of user–transformer association identification reaches approximately 93% under the available field-data conditions. Comparative and robustness analyses further indicate that Fisher optimal segmentation maintains relatively stable performance under the tested missing-entry and reduced class-separation conditions. These results suggest that the proposed framework provides a feasible and interpretable approach to topology identification in complex low-voltage distribution networks.
Förderung
- National Natural Science Foundation of China
- Key Research and Development Program of Shandong Province
- Shandong Provincial Excellent Educational and Teaching Resources Program for Postgraduates
Zitieren
APA
Lv, C., Zhang, B., Luo, W., Xi, J., & Fan, D. (2026). Topology Identification Method for Distribution Networks Based on Improved T-Type Grey Relational Analysis and Fisher Optimal Segmentation. Energies, 19(15), 3524. https://doi.org/10.3390/en19153524
Vancouver
Lv C, Zhang B, Luo W, Xi J, Fan D. Topology Identification Method for Distribution Networks Based on Improved T-Type Grey Relational Analysis and Fisher Optimal Segmentation. Energies. 2026;19(15):3524. doi:10.3390/en19153524
BibTeX
@article{Lv2026,
author = {Lv, Changzhi and Zhang, Bodong and Luo, Weiqiang and Xi, Jiahong and Fan, Di},
title = {Topology Identification Method for Distribution Networks Based on Improved T-Type Grey Relational Analysis and Fisher Optimal Segmentation},
journal = {Energies},
year = {2026},
volume = {19},
number = {15},
pages = {3524},
doi = {10.3390/en19153524}
}
EUVIMED