EUVIMEDEUVIMED entdecken
Open Access · CC BY 4.0

An Invertible Extended Sequence Transform for Untransposed Three-Phase Overhead Lines

Jozef Bendík, Matej Cenký

Energies · 06.07.2026 · 19 (13) · 3203

DOI: 10.3390/en19133203 ↗

Kurz gefasst

Fachartikel in der Zeitschrift Energies, online erschienen am 06.07.2026. Verfasst von Jozef Bendík und 1 weiteren Autor:innen. Die Arbeit nennt 19 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0). Gefördert von: The Scientific Grant Agency.

AbstractBibliografische AngabenZitierenVerwandte Studien

Abstract (Originalsprache)

The classical Fortescue symmetrical-component transform remains fully invertible as a similarity transform when the complete sequence-domain matrix is retained. In practice, however, untransposed three-phase overhead lines are often summarized by the diagonal sequence quantities Z0 and Z1, while the asymmetry appears through coupled off-diagonal terms that are less convenient for compact parameterization and measurement-based interpretation. This paper presents an Extended Sequence Transform that reorganizes the six independent entries of the phase-domain impedance matrix into six structured parameters by means of a lossless, invertible 6×6 linear mapping. The first two parameters are identical to the classical zero- and positive-sequence impedances, which preserves backward compatibility. The remaining four parameters isolate asymmetry information in a form from which all entries of the classical sequence matrix can be recovered exactly, and from which the full phase-domain matrix is reconstructed to machine precision. The proposed representation does not diagonalize an untransposed line; rather, it provides a compact and explicit six-scalar parameterization that separates the classical sequence pair from four asymmetry descriptors. Numerical validation on a 50 km untransposed overhead line confirms exact round-trip reconstruction and exact agreement of the unbalance factors obtained from the classical and extended representations. A stochastic perturbation study further shows that round-trip reconstruction remains at numerical precision and that, within the tested perturbation grid, the M2 factor is more sensitive than M0. Line-constant calculations performed in OpenDSS for two typical 400 kV tower geometries link the four asymmetry parameters to specific geometric features, a worked offline measurement example recovers them from simulated three-phase terminal tests, and a distributed-model study confirms that the lumped-parameter description of the asymmetry remains accurate to within about 0.6% up to 150 km.

Förderung

  • The Scientific Grant Agency

Zitieren

APA

Bendík, J., & Cenký, M. (2026). An Invertible Extended Sequence Transform for Untransposed Three-Phase Overhead Lines. Energies, 19(13), 3203. https://doi.org/10.3390/en19133203

Vancouver

Bendík J, Cenký M. An Invertible Extended Sequence Transform for Untransposed Three-Phase Overhead Lines. Energies. 2026;19(13):3203. doi:10.3390/en19133203

BibTeX
@article{Bendk2026,
  author = {Bendík, Jozef and Cenký, Matej},
  title = {An Invertible Extended Sequence Transform for Untransposed Three-Phase Overhead Lines},
  journal = {Energies},
  year = {2026},
  volume = {19},
  number = {13},
  pages = {3203},
  doi = {10.3390/en19133203}
}
Kostenlos starten →