Simulation Study on the Electric-Field Distortion Induced by Typical Assembly Defects in Cable Terminals
Energies · 02.07.2026 · 19 (13) · 3143
DOI: 10.3390/en19133143 ↗Kurz gefasst
Fachartikel in der Zeitschrift Energies, online erschienen am 02.07.2026. Verfasst von Xin Yu und 5 weiteren Autor:innen. Die Arbeit nennt 24 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0). Gefördert von: Innovation Project of China Southern Power Grid Co., Ltd..
Abstract (Originalsprache)
As a critical insulation component in cable systems, the cable terminal is susceptible to defects caused by human and environmental factors during manufacturing, installation, and service. Such defects may lead to local electric-field distortion and insulation weaknesses at the cable terminal, posing a severe threat to the safe operation of the cable system. In this study, an electric-field simulation model of a 10 kV cable terminal was implemented to investigate the effects of various defects, such as insufficient stress-cone overlap, axial scratch, ring-cut defect, and moisture ingress on the cable terminal. The results show that insufficient stress-cone overlap produces a severe field distortion, and the distortion level is strongly correlated with the misalignment distance. For mechanical damage defects, axial scratches and ring-cut defects mainly distort the electric field inside the air gap, and defect position induces a stronger distortion level than that of defect depth. With increasing ring-cut depth, the maximum value of distorted electric field first decreases and then rises slightly. For moisture defects, the distorted field primarily occurs at the angle between the water-film tip and the stress cone, where the maximum value appears near the XLPE/SIR interface. These results provide a theoretical basis for defect diagnosis, structural optimization, and assembly process control of cable terminals.
Förderung
- Innovation Project of China Southern Power Grid Co., Ltd.
Zitieren
APA
Yu, X., Ren, Q., Li, Y., Yang, M., Yu, S., & Zhao, X. (2026). Simulation Study on the Electric-Field Distortion Induced by Typical Assembly Defects in Cable Terminals. Energies, 19(13), 3143. https://doi.org/10.3390/en19133143
Vancouver
Yu X, Ren Q, Li Y, Yang M, Yu S, Zhao X. Simulation Study on the Electric-Field Distortion Induced by Typical Assembly Defects in Cable Terminals. Energies. 2026;19(13):3143. doi:10.3390/en19133143
BibTeX
@article{Yu2026,
author = {Yu, Xin and Ren, Qiyuan and Li, Yinge and Yang, Mingyuan and Yu, Shihu and Zhao, Xuetong},
title = {Simulation Study on the Electric-Field Distortion Induced by Typical Assembly Defects in Cable Terminals},
journal = {Energies},
year = {2026},
volume = {19},
number = {13},
pages = {3143},
doi = {10.3390/en19133143}
}
EUVIMED