Transient instability during the low-voltage ride-through (LVRT) recovery of permanent magnet synchronous generator (PMSG) wind turbines is strongly influenced by weak-grid interactions, while the quantitative relationship among grid strength, control parameters, and recovery performance remains insufficiently understood. This paper develops a small-signal transient recovery characteristic matrix for a grid-connected PMSG system by incorporating the dynamic interactions among the phase-locked loop (PLL), inner current loop, DC-link voltage loop, and grid-side inductance. Dominant-mode and root-locus analyses are employed to investigate how variations in the short-circuit ratio (SCR) affect dominant eigenvalue trajectories and the sensitivities of six PI control parameters. Based on the identified dynamic mechanisms, an SCR-adaptive sensitivity-guided particle swarm optimization (SG-PSO) method is proposed for coordinated PI parameter tuning. The proposed approach introduces SCR-dependent damping constraints and physical feasibility constraints, while normalized real-part eigenvalue sensitivities are utilized to guide the optimization process toward the most influential control parameters. Comparative simulation results demonstrate that, under SCR = 1.5, SG-PSO reduces the point of common coupling (PCC) voltage overshoot to 1.4% and shortens the recovery time to 58 ms, achieving better transient recovery indices than conventional PSO and OOBO-PI under the same simulation and constraint settings. Under SCR = 2.5, the recovery time is further reduced to 46 ms while maintaining a low overshoot of 0.9%. Additional robustness tests under parameter uncertainties and fault-condition variations further support the effectiveness and adaptability of the proposed method. The results indicate that the proposed SG-PSO framework provides an effective solution for enhancing LVRT recovery performance of PMSG wind turbines operating in weak-grid environments.

Zitieren

APA

Han, X., Feng, X., Huang, T., Liu, Z., & Chen, B. (2026). Dominant-Mode-Based SCR-Adaptive SG-PSO Tuning for LVRT Recovery of PMSG Wind Turbines in Weak Grids. Energies, 19(13), 3081. https://doi.org/10.3390/en19133081

Vancouver

Han X, Feng X, Huang T, Liu Z, Chen B. Dominant-Mode-Based SCR-Adaptive SG-PSO Tuning for LVRT Recovery of PMSG Wind Turbines in Weak Grids. Energies. 2026;19(13):3081. doi:10.3390/en19133081

BibTeX
@article{Han2026,
  author = {Han, Xiao and Feng, Xinghao and Huang, Tong and Liu, Zixuan and Chen, Butian},
  title = {Dominant-Mode-Based SCR-Adaptive SG-PSO Tuning for LVRT Recovery of PMSG Wind Turbines in Weak Grids},
  journal = {Energies},
  year = {2026},
  volume = {19},
  number = {13},
  pages = {3081},
  doi = {10.3390/en19133081}
}
Kostenlos starten →