EUVIMEDEUVIMED entdecken
Open Access · CC BY 4.0

Optimal Capacity Allocation of Pumped Hydro Storage Towards Long-Term High-Penetration Renewable Energy Integration: A Case Study of a Coastal Power Grid

Jiquan Chen, Jinxia Yu, Han Qin, Guobin Ye

Energies · 25.06.2026 · 19 (13) · 2982

DOI: 10.3390/en19132982 ↗

Kurz gefasst

Fachartikel in der Zeitschrift Energies, online erschienen am 25.06.2026. Verfasst von Jiquan Chen und 3 weiteren Autor:innen. Die Arbeit wurde bisher 1-mal zitiert (Crossref) und nennt 26 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0). Gefördert von: Carbon Neutrality and Energy System Transformation.

AbstractBibliografische AngabenZitierenVerwandte Studien

Abstract (Originalsprache)

The integration of high-penetration renewable energy creates new requirements for cross-timescale peak shaving and for system robustness under extreme meteorological conditions. This study develops a dual-timescale capacity allocation method for pumped hydro storage (PHS), combining 8760 h chronological production simulation with monthly typical-day retrospective analysis. The model represents the operating limits of conventional units, nuclear power, hydropower, wind power, photovoltaic generation, tie-line exchange, and PHS energy shifting. On this basis, a stepwise capacity-sensitivity framework is established to minimize annualized comprehensive system cost while controlling renewable energy curtailment within a predefined planning threshold, rather than treating zero curtailment as an unconditional monthly hard constraint. Using long-term planning data from a coastal provincial power grid in southeastern China, the study compares the 2035 and 2040 planning scenarios. The results show that isolated typical-day models tend to overestimate PHS requirements because they disconnect chronological continuity and cross-day reservoir buffering. In 2035, the system presents a two-level seasonal capacity structure: 15,000 MW can support normalized operation in stable months, whereas the rigid boundary rises to 19,000 MW under extreme autumn high-wind conditions. In 2040, wind and photovoltaic capacity increase by approximately 20.01 GW compared with 2035, deepening low-net-load valleys and compressing seasonal regulation margins. Under the assumed planning boundary, the recommended PHS capacity converges to 23,000 MW. The proposed framework provides a practical reference for flexible resource planning in coastal power grids with deep renewable energy integration.

Förderung

  • Carbon Neutrality and Energy System Transformation

Zitieren

APA

Chen, J., Yu, J., Qin, H., & Ye, G. (2026). Optimal Capacity Allocation of Pumped Hydro Storage Towards Long-Term High-Penetration Renewable Energy Integration: A Case Study of a Coastal Power Grid. Energies, 19(13), 2982. https://doi.org/10.3390/en19132982

Vancouver

Chen J, Yu J, Qin H, Ye G. Optimal Capacity Allocation of Pumped Hydro Storage Towards Long-Term High-Penetration Renewable Energy Integration: A Case Study of a Coastal Power Grid. Energies. 2026;19(13):2982. doi:10.3390/en19132982

BibTeX
@article{Chen2026,
  author = {Chen, Jiquan and Yu, Jinxia and Qin, Han and Ye, Guobin},
  title = {Optimal Capacity Allocation of Pumped Hydro Storage Towards Long-Term High-Penetration Renewable Energy Integration: A Case Study of a Coastal Power Grid},
  journal = {Energies},
  year = {2026},
  volume = {19},
  number = {13},
  pages = {2982},
  doi = {10.3390/en19132982}
}