Stability Analysis and Oscillation Mitigation of Grid-Forming Doubly Fed Induction Systems Based on Reduced-Order Modeling Generator
Energies · 21.06.2026 · 19 (12) · 2927
DOI: 10.3390/en19122927 ↗Kurz gefasst
Fachartikel in der Zeitschrift Energies, online erschienen am 21.06.2026. Verfasst von Jingjia Liu und 5 weiteren Autor:innen. Die Arbeit wurde bisher 1-mal zitiert (Crossref) und nennt 19 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0). Gefördert von: National Energy Group Science and Technology Project.
Abstract (Originalsprache)
The increasing penetration of renewable energy exposes doubly fed induction generator (DFIG)-based wind power systems to weak-grid conditions, making them susceptible to low-frequency and subsynchronous oscillations. Although grid-forming (GFM) control enhances weak-grid adaptability, the resulting high-order small-signal model complicates stability analysis and controller design. This paper establishes a 15th-order state-space model for a GFM-DFIG system. Eigenvalue analysis is performed to identify the dominant oscillation modes and to reveal their sensitivity to controller parameters and grid strength. To reduce computational burden, a model order reduction method combining singular perturbation theory and participation factor analysis is proposed, yielding an eighth-order model that preserves dominant oscillatory characteristics. An additional damping control strategy is then designed using the reduced model. Simulations validate the reduced model’s accuracy and demonstrate the damping control’s effectiveness in mitigating oscillations. This paper provides an effective framework for stability analysis, reduced-order modeling, and damping control design for GFM-DFIG systems.
Förderung
- National Energy Group Science and Technology Project
Zitieren
APA
Liu, J., Zhao, L., Chu, J., Zhu, H., Sun, Z., & Yu, Y. (2026). Stability Analysis and Oscillation Mitigation of Grid-Forming Doubly Fed Induction Systems Based on Reduced-Order Modeling Generator. Energies, 19(12), 2927. https://doi.org/10.3390/en19122927
Vancouver
Liu J, Zhao L, Chu J, Zhu H, Sun Z, Yu Y. Stability Analysis and Oscillation Mitigation of Grid-Forming Doubly Fed Induction Systems Based on Reduced-Order Modeling Generator. Energies. 2026;19(12):2927. doi:10.3390/en19122927
BibTeX
@article{Liu2026,
author = {Liu, Jingjia and Zhao, Lulu and Chu, Jingchun and Zhu, Haitao and Sun, Zhenxin and Yu, Yiping},
title = {Stability Analysis and Oscillation Mitigation of Grid-Forming Doubly Fed Induction Systems Based on Reduced-Order Modeling Generator},
journal = {Energies},
year = {2026},
volume = {19},
number = {12},
pages = {2927},
doi = {10.3390/en19122927}
}