An Equivalent Model for Cooling Tower Boundary Conditions in Industrial Recirculating Cooling Water Systems
Energies · 16.05.2026 · 19 (10) · 2400
DOI: 10.3390/en19102400 ↗Kurz gefasst
Fachartikel in der Zeitschrift Energies, online erschienen am 16.05.2026. Verfasst von Wei Huang und 6 weiteren Autor:innen. Die Arbeit wurde bisher 1-mal zitiert (Crossref) und nennt 32 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0). Gefördert von: National Key R&D Program of China, National Natural Science Foundation of China, Ganpo Talent Support Program.
Abstract (Originalsprache)
To mitigate the risks of pressure surges and water hammer during accidental pump trips in industrial cooling water systems, accurate boundary modeling of cooling towers is essential. This study employs the Method of Characteristics (MOC) to evaluate four equivalent models for the central riser shaft: Model A (constant level), Model B (two-way surge tank), Model C (dynamic coupling of shaft and distribution channel), and Model D (composite structure). Results indicate that Model A fails to reflect actual hydraulic states, producing an unrealistic pump reverse speed of −253.24 r/min and overly conservative estimates. While Models B, C, and D exhibit similar pressure trends, Model C most accurately captures the physical drainage process, realistically simulating how the shaft level stabilizes at the distribution channel elevation before declining. By accurately reflecting engineering hydraulics, Model C provides the most reliable basis for water hammer safety assessments. It is recommended for optimizing pump valve closure strategies, vacuum breaker installations, and siphon protection designs in power plant systems.
Förderung
- National Key R&D Program of China
- National Natural Science Foundation of China
- Ganpo Talent Support Program
- Natural Science Foundation of Jiangxi Province
Zitieren
APA
Huang, W., Chen, Y., Li, H., He, Z., Li, Z., Liu, B., & Wang, G. (2026). An Equivalent Model for Cooling Tower Boundary Conditions in Industrial Recirculating Cooling Water Systems. Energies, 19(10), 2400. https://doi.org/10.3390/en19102400
Vancouver
Huang W, Chen Y, Li H, He Z, Li Z, Liu B, et al. An Equivalent Model for Cooling Tower Boundary Conditions in Industrial Recirculating Cooling Water Systems. Energies. 2026;19(10):2400. doi:10.3390/en19102400
BibTeX
@article{Huang2026,
author = {Huang, Wei and Chen, Yucong and Li, Huokun and He, Zhongzheng and Li, Zhe and Liu, Bo and Wang, Gang},
title = {An Equivalent Model for Cooling Tower Boundary Conditions in Industrial Recirculating Cooling Water Systems},
journal = {Energies},
year = {2026},
volume = {19},
number = {10},
pages = {2400},
doi = {10.3390/en19102400}
}