EUVIMEDEUVIMED entdecken
Open Access · CC BY 4.0

Field Tests and Applicability Analysis of an Underground Cooling Installation Powered by Ventilation Air Methane (VAM)

Robert Hildebrandt, Marcin Smołka, Wodzisław Piekarczyk, Krzysztof Skrzypkowski

Energies · 18.03.2026 · 19 (6) · 1511

DOI: 10.3390/en19061511 ↗

Kurz gefasst

Fachartikel in der Zeitschrift Energies, online erschienen am 18.03.2026. Verfasst von Robert Hildebrandt und 3 weiteren Autor:innen. Die Arbeit wurde bisher 1-mal zitiert (Crossref) und nennt 28 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0). Gefördert von: National Research Centre, AGH University of Krakow.

AbstractBibliografische AngabenZitierenVerwandte Studien

Abstract (Originalsprache)

Modern underground hard coal mines encounter increasing natural hazards as mining depth increases, including, in particular, significant rises in both methane and thermal hazards. Thermal threats are common in Polish mines, especially in areas where the primary rock temperature exceeds 40 °C. To provide an energy source for cooling systems and reduce methane emissions from ventilation air, a system based on a catalytic reactor combined with an absorption chiller was developed. Field tests conducted at the experimental mine Barbara in Mikołów (Poland) indicate that a COP based on methane chemical energy can reach a level of 0.3–0.4. An application analysis was conducted based on the results of cross-sectional forecasts of climatic conditions (thermal conditions forecasts). The results indicate the potential for using this installation as a supporting component of mine cooling systems. An important factor that may limit the efficiency of the installation is the volume flow of the exhaust air stream. It is estimated that, in countries where, as in Poland, air temperature is the primary criterion for assessing thermal safety, the results of the analysis would be similar.

Förderung

  • National Research Centre
  • AGH University of Krakow

Zitieren

APA

Hildebrandt, R., Smołka, M., Piekarczyk, W., & Skrzypkowski, K. (2026). Field Tests and Applicability Analysis of an Underground Cooling Installation Powered by Ventilation Air Methane (VAM). Energies, 19(6), 1511. https://doi.org/10.3390/en19061511

Vancouver

Hildebrandt R, Smołka M, Piekarczyk W, Skrzypkowski K. Field Tests and Applicability Analysis of an Underground Cooling Installation Powered by Ventilation Air Methane (VAM). Energies. 2026;19(6):1511. doi:10.3390/en19061511

BibTeX
@article{Hildebrandt2026,
  author = {Hildebrandt, Robert and Smołka, Marcin and Piekarczyk, Wodzisław and Skrzypkowski, Krzysztof},
  title = {Field Tests and Applicability Analysis of an Underground Cooling Installation Powered by Ventilation Air Methane (VAM)},
  journal = {Energies},
  year = {2026},
  volume = {19},
  number = {6},
  pages = {1511},
  doi = {10.3390/en19061511}
}