EUVIMEDEUVIMED entdecken
Open Access · CC BY 4.0

Strategies to Mitigate Reverse Power Flow in Distribution Networks with High Penetration of Solar Photovoltaic Generation

Ivan Santos Pereira, Gustavo da Costa Vergara, Jesús M. López-Lezama, Nicolás Muñoz-Galenao, Lina Paola Garcés Negrete

Energies · 19.02.2026 · 19 (4) · 1069

DOI: 10.3390/en19041069 ↗

Kurz gefasst

Fachartikel in der Zeitschrift Energies, online erschienen am 19.02.2026. Verfasst von Ivan Santos Pereira und 4 weiteren Autor:innen. Die Arbeit wurde bisher 8-mal zitiert (Crossref) und nennt 29 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0). Gefördert von: Programa de Apoio à Pós-Graduação (PROAP) of CAPES—Coordenação de Aperfeiçoamento de Pessoal de Nível Superior.

AbstractBibliografische AngabenZitierenVerwandte Studien

Abstract (Originalsprache)

The power industry has undergone significant recent changes due to the growing demand for a cleaner and more sustainable energy mix. In this context, the Brazilian government began encouraging distributed generation (DG), making photovoltaic generation a strong trend in the country. However, the expansion of DG may cause negative impacts on the grid, such as reverse power flow (RPF) and overvoltages, which motivates research aimed at mitigating these effects. This study proposes strategies to mitigate RPF in distribution networks with high penetration of photovoltaic generation and evaluates their impacts on the electrical system. Three strategies were analyzed: a battery energy storage system (BESS), a control mechanism using a Grid Zero inverter, and PV Curtailment. The strategies were implemented in OpenDSS on a real distribution network located in São Paulo, Brazil. The assessment involved analyzing power flow in critical transformers and at the substation, as well as monitoring bus voltages and network energy losses. The quantitative results demonstrate that BESS allocation was the superior strategy, reducing technical losses by 61.3% and fully mitigating reverse power flow under steady-state conditions. The Grid Zero inverter eliminated power injection into the grid; however, it increased substation dependency by 59% compared to the baseline scenario. PV curtailment, although achieving the smallest reduction in RPF, proved to be the most effective technique for power quality, limiting the average voltage rise to 0.7%.

Förderung

  • Programa de Apoio à Pós-Graduação (PROAP) of CAPES—Coordenação de Aperfeiçoamento de Pessoal de Nível Superior

Zitieren

APA

Pereira, I. S., Vergara, G. D. C., López-Lezama, J. M., Muñoz-Galenao, N., & Negrete, L. P. G. (2026). Strategies to Mitigate Reverse Power Flow in Distribution Networks with High Penetration of Solar Photovoltaic Generation. Energies, 19(4), 1069. https://doi.org/10.3390/en19041069

Vancouver

Pereira IS, Vergara GDC, López-Lezama JM, Muñoz-Galenao N, Negrete LPG. Strategies to Mitigate Reverse Power Flow in Distribution Networks with High Penetration of Solar Photovoltaic Generation. Energies. 2026;19(4):1069. doi:10.3390/en19041069

BibTeX
@article{Pereira2026,
  author = {Pereira, Ivan Santos and Vergara, Gustavo da Costa and López-Lezama, Jesús M. and Muñoz-Galenao, Nicolás and Negrete, Lina Paola Garcés},
  title = {Strategies to Mitigate Reverse Power Flow in Distribution Networks with High Penetration of Solar Photovoltaic Generation},
  journal = {Energies},