Gramian Angular Field–Gramian Adversial Network–ResNet34: High-Accuracy Fault Diagnosis for Transformer Windings with Limited Samples

Hongwen Liu, Kun Yang, Guochao Qian, Jin Hu, Weiju Dai, Liang Zhu, Tao Guo, Jun Shi, Dongyang Wang

Energies · 14.08.2025 · 18 (16) · 4329

DOI: 10.3390/en18164329 ↗

Kurz gefasst

Fachartikel in der Zeitschrift Energies, online erschienen am 14.08.2025. Verfasst von Hongwen Liu und 8 weiteren Autor:innen. Die Arbeit wurde bisher 4-mal zitiert (Crossref) und nennt 29 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0). Gefördert von: the Electric Power Research Institute of Yunnan Power Grid.

AbstractBibliografische AngabenZitierenVerwandte Studien

Abstract (Originalsprache)

Transformers are critical equipment in power transmission and distribution systems, and the condition of their windings significantly impacts their reliable operation. Therefore, the fault diagnosis of transformer windings is of great importance. Addressing the challenge of limited fault samples in traditional diagnostic methods, this study proposes a small-sample fault diagnosis method for transformer windings. This method combines data augmentation using the Gramian angular field (GAF) and generative adversarial networks (GAN) with a deep residual network (ResNet). First, by establishing a transformer winding fault simulation experiment platform, frequency response curves for three types of faults—axial displacement, bulging and warping, and cake-to-cake short circuits—and different fault regions were obtained using the frequency response analysis method (FRA). Second, a frequency response curve image conversion technique based on the Gramian angular field was proposed, converting the frequency response curves into Gramian angular summation field (GASF) and Gramian angular difference field (GADF) images using the Gramian angular field. Next, we introduce several improved GANs to augment the frequency response data and evaluate the quality of the generated samples. We compared and analysed the diagnostic accuracy of ResNet34 networks trained using different GAF–GAN combination datasets for winding fault types, and we proposed a transformer winding small-sample fault diagnosis method based on GAF-GAN-ResNet34, which can achieve a fault identification accuracy rate of 96.88% even when using only 28 real samples. Finally, we applied the proposed fault diagnosis method to on-site transformers to verify its classification performance under small-sample conditions. The results show that, even with insufficient fault samples, the proposed method can achieve high diagnostic accuracy.

Förderung

  • the Electric Power Research Institute of Yunnan Power Grid

Zitieren

APA

Liu, H., Yang, K., Qian, G., Hu, J., Dai, W., Zhu, L., Guo, T., Shi, J., & Wang, D. (2025). Gramian Angular Field–Gramian Adversial Network–ResNet34: High-Accuracy Fault Diagnosis for Transformer Windings with Limited Samples. Energies, 18(16), 4329. https://doi.org/10.3390/en18164329

Vancouver

Liu H, Yang K, Qian G, Hu J, Dai W, Zhu L, et al. Gramian Angular Field–Gramian Adversial Network–ResNet34: High-Accuracy Fault Diagnosis for Transformer Windings with Limited Samples. Energies. 2025;18(16):4329. doi:10.3390/en18164329

BibTeX
@article{Liu2025,
  author = {Liu, Hongwen and Yang, Kun and Qian, Guochao and Hu, Jin and Dai, Weiju and Zhu, Liang and Guo, Tao and Shi, Jun and Wang, Dongyang},
  title = {Gramian Angular Field–Gramian Adversial Network–ResNet34: High-Accuracy Fault Diagnosis for Transformer Windings with Limited Samples},
  journal = {Energies},
  year = {2025},
  volume = {18},
  number = {16},
  pages = {4329},
  doi = {10.3390/en18164329}
}