Experimental Investigation of Heat Pump Modules Limited to 150 g of Refrigerant R290 and a Dedicated Test Rig
Energies · 10.05.2025 · 18 (10) · 2455
DOI: 10.3390/en18102455 ↗Kurz gefasst
Fachartikel in der Zeitschrift Energies, online erschienen am 10.05.2025. Verfasst von Stephan Preisinger und 6 weiteren Autor:innen. Die Arbeit wurde bisher 2-mal zitiert (Crossref) und nennt 16 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0). Gefördert von: Austrian Research Promotion Agency (FFG).
Abstract (Originalsprache)
Heat pumps are widely regarded as a key technology for sustainable heating, offering a pathway to significantly reduce fossil fuel dependency and combat the climate crisis. However, replacing individual gas boilers with heat pumps in multi-unit residential buildings remains a substantial challenge despite its immense potential to lower urban greenhouse gas emissions. To address this, the following paper describes the development of a compact, modular heat pump system designed to replace conventional gas boilers, focusing on the building and testing of a prototype for such a modular heat pump system. The prototype supports multiple functionalities, including space heating, cooling, and domestic hot water production. The performance advantages of two different compressor technologies were exploited to optimize the efficiency of the complete system and the pressure lifts associated with applications for heating and domestic hot water production. Thus, measurements were conducted across a range of operating points, comparing different heat pump module types. In the case of the piston compressor module, the Carnot efficiency was in the range of 47.2% to 50.4%. The total isentropic efficiency for floor heating and domestic hot water production was above 0.45 for both piston and rotary compressors.
Förderung
- Austrian Research Promotion Agency (FFG)
Zitieren
APA
Preisinger, S., Lauermann, M., Schwarzfurtner, M., Fischer, S., Kling, S., Moisi, H., & Reichl, C. (2025). Experimental Investigation of Heat Pump Modules Limited to 150 g of Refrigerant R290 and a Dedicated Test Rig. Energies, 18(10), 2455. https://doi.org/10.3390/en18102455
Vancouver
Preisinger S, Lauermann M, Schwarzfurtner M, Fischer S, Kling S, Moisi H, et al. Experimental Investigation of Heat Pump Modules Limited to 150 g of Refrigerant R290 and a Dedicated Test Rig. Energies. 2025;18(10):2455. doi:10.3390/en18102455
BibTeX
@article{Preisinger2025,
author = {Preisinger, Stephan and Lauermann, Michael and Schwarzfurtner, Micha and Fischer, Sebastian and Kling, Stephan and Moisi, Heinz and Reichl, Christoph},
title = {Experimental Investigation of Heat Pump Modules Limited to 150 g of Refrigerant R290 and a Dedicated Test Rig},
journal = {Energies},
year = {2025},
volume = {18},
number = {10},
pages = {2455},
doi = {10.3390/en18102455}
}