A Detection Method for Slight Inter-Turn Short-Circuit Fault in Dry-Type Air-Core Shunt Reactors
Energies · 03.04.2024 · 17 (7) · 1709
DOI: 10.3390/en17071709 ↗Kurz gefasst
Fachartikel in der Zeitschrift Energies, online erschienen am 03.04.2024. Verfasst von Jie Wu und 6 weiteren Autor:innen. Die Arbeit wurde bisher 12-mal zitiert (Crossref) und nennt 30 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0). Gefördert von: State Grid Sichuan Electric Power Company scientific project.
Abstract (Originalsprache)
Dry-type air-core shunt reactors are integral components in power transmission and distribution networks, designed to control reactive power and enhance system stability. However, inter-turn short-circuit faults (ISCFs) are common occurrences in shunt reactors, which are caused by various factors, including manufacturing defects, insulation degradation, or operational stresses. At the early stage of the ISCFs, the current does not reach a sufficient level to activate the protective equipment. These faults may lead to serious consequences, such as overheating, insulation breakdown, and even catastrophic failures, posing risks to the entire power system. Therefore, developing an effective and reliable detection method for ISCFs at the early stage is paramount. In this paper, a new method named the fault detection factor (FDF) based on equivalent resistance is presented to detect the slight ISCFs in dry-type air-core shunt reactors considering insulation resistance. In addition, the effect of noise signal existence in the monitoring process is taken into account. A moving average filter is adopted to guarantee both the sensitivity and the reliability of the proposed method. Ultimately, the simulation results of the FDF under different conditions are presented, which show the effectiveness and potential of the proposed method in observing and monitoring slight ISCFs.
Förderung
- State Grid Sichuan Electric Power Company scientific project
Zitieren
APA
Wu, J., Zhen, W., Chang, Z., Zhang, M., Peng, Y., Liu, Y., & Huang, Q. (2024). A Detection Method for Slight Inter-Turn Short-Circuit Fault in Dry-Type Air-Core Shunt Reactors. Energies, 17(7), 1709. https://doi.org/10.3390/en17071709
Vancouver
Wu J, Zhen W, Chang Z, Zhang M, Peng Y, Liu Y, et al. A Detection Method for Slight Inter-Turn Short-Circuit Fault in Dry-Type Air-Core Shunt Reactors. Energies. 2024;17(7):1709. doi:10.3390/en17071709
BibTeX
@article{Wu2024,
author = {Wu, Jie and Zhen, Wei and Chang, Zhengwei and Zhang, Man and Peng, Yumin and Liu, Ying and Huang, Qi},
title = {A Detection Method for Slight Inter-Turn Short-Circuit Fault in Dry-Type Air-Core Shunt Reactors},
journal = {Energies},
year = {2024},
volume = {17},
number = {7},
pages = {1709},
doi = {10.3390/en17071709}
}