Fachartikel in der Zeitschrift Energies, online erschienen am 03.03.2024. Verfasst von Tong Zhu und 7 weiteren Autor:innen. Die Arbeit wurde bisher 14-mal zitiert (Crossref) und nennt 24 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0). Gefördert von: Science and Technology Project of State Grid Corporation of China.

AbstractBibliografische AngabenZitierenVerwandte Studien

Abstract (Originalsprache)

In photovoltaic grid-connected systems, the interaction between grid-connected inverters and the grid may cause harmonic oscillation, which severely affects the normal operation of the system. To improve the quality of the output electrical energy, photovoltaic grid-connected systems often use LCL filters as output filters to filter out high-frequency harmonics. Taking the three-phase LCL-type photovoltaic grid-connected inverter system as an example, this paper addresses the issue of harmonic resonance. Firstly, based on the harmonic linearization method and considering the impact of the coupling compensation term on the grid-side voltage, a modular positive and negative sequence impedance modeling method is proposed, which simplifies the secondary modeling process of the converter under feedback control. Then, the stability analysis is conducted using the Nyquist criterion, revealing the mechanism of high-frequency resonance in photovoltaic grid-connected systems. Furthermore, this paper delves into the impact of changes in system parameters on impedance characteristics and system stability. The results indicate that the proportional coefficient of the internal loop current controller has a significant influence on system impedance characteristics. Additionally, this paper proposes an active damping design method that combines lead correction and capacitor current feedback to impedance-reconstruct the easily oscillating frequency band. Finally, the effectiveness of this method is verified in the simulation platform. Simulation results confirm the effectiveness of this method in suppressing harmonic resonance while maintaining rapid dynamic response.

Förderung

  • Science and Technology Project of State Grid Corporation of China

Zitieren

APA

Zhu, T., Huang, G., Ouyang, X., Zhang, W., Wang, Y., Ye, X., Wang, Y., & Gao, S. (2024). Analysis and Suppression of Harmonic Resonance in Photovoltaic Grid-Connected Systems. Energies, 17(5), 1218. https://doi.org/10.3390/en17051218

Vancouver

Zhu T, Huang G, Ouyang X, Zhang W, Wang Y, Ye X, et al. Analysis and Suppression of Harmonic Resonance in Photovoltaic Grid-Connected Systems. Energies. 2024;17(5):1218. doi:10.3390/en17051218

BibTeX
@article{Zhu2024,
  author = {Zhu, Tong and Huang, Gechao and Ouyang, Xuetong and Zhang, Weilin and Wang, Yanfeng and Ye, Xi and Wang, Yuhong and Gao, Shilin},
  title = {Analysis and Suppression of Harmonic Resonance in Photovoltaic Grid-Connected Systems},
  journal = {Energies},
  year = {2024},
  volume = {17},
  number = {5},
  pages = {1218},
  doi = {10.3390/en17051218}
}
Kostenlos starten →