Early Detection of Health Condition Degradation of Circuit Breaker Based on Electrical Quantity Monitoring
Energies · 24.07.2023 · 16 (14) · 5581
DOI: 10.3390/en16145581 ↗Kurz gefasst
Fachartikel in der Zeitschrift Energies, online erschienen am 24.07.2023. Verfasst von Lisheng Li und 5 weiteren Autor:innen. Die Arbeit wurde bisher 12-mal zitiert (Crossref) und nennt 27 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0). Gefördert von: State Grid Shandong Electric Power Corporation.
Abstract (Originalsprache)
Circuit breakers on the filter bank branches in converter stations are vulnerable to contact wear and mechanical deterioration caused by frequent operations, which can lead to circuit breaker breakdowns and explosions. It is imperative to conduct research on the early detection of abnormal states in circuit breakers. Existing electrical quantity-based detection methods are constrained by a priori assumptions, and their measurement methods are susceptible to interference, leading to misjudgments. To address this issue, this paper examines the influence of changes in critical breakdown field strength and contact spacing on circuit breaker operation states. It also proposes a technical scheme that employs breakdown current values to comprehensively characterize circuit breaker operation states, replacing the use of critical breakdown field strength and contact spacing. An early detection method for abnormal circuit breaker states based on a sequence of breakdown current ratios at different times is proposed, and its effectiveness is verified through simulation and field recording data.
Förderung
- State Grid Shandong Electric Power Corporation
Zitieren
APA
Li, L., Wang, B., Liu, Y., Yu, H., Zhang, S., & Huang, M. (2023). Early Detection of Health Condition Degradation of Circuit Breaker Based on Electrical Quantity Monitoring. Energies, 16(14), 5581. https://doi.org/10.3390/en16145581
Vancouver
Li L, Wang B, Liu Y, Yu H, Zhang S, Huang M. Early Detection of Health Condition Degradation of Circuit Breaker Based on Electrical Quantity Monitoring. Energies. 2023;16(14):5581. doi:10.3390/en16145581
BibTeX
@article{Li2023,
author = {Li, Lisheng and Wang, Bin and Liu, Yang and Yu, Haidong and Zhang, Shidong and Huang, Min},
title = {Early Detection of Health Condition Degradation of Circuit Breaker Based on Electrical Quantity Monitoring},
journal = {Energies},
year = {2023},
volume = {16},
number = {14},
pages = {5581},
doi = {10.3390/en16145581}
}
EUVIMED