Modelling Electro-Mechanical Behaviour of an XLPE Insulation Layer for Hi-Voltage Composite Power Cables: Effect of Voids on Onset of Coalescence

Michele Miceli, Valter Carvelli, Monssef Drissi-Habti

Energies · 09.06.2023 · 16 (12) · 4620

DOI: 10.3390/en16124620 ↗

Kurz gefasst

Fachartikel in der Zeitschrift Energies, online erschienen am 09.06.2023. Verfasst von Michele Miceli und 2 weiteren Autor:innen. Die Arbeit wurde bisher 14-mal zitiert (Crossref) und nennt 11 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0). Gefördert von: Flow-Cam MarTERA Era-Net Project.

AbstractBibliografische AngabenZitierenVerwandte Studien

Abstract (Originalsprache)

The harshness of the submarine environment represents a serious threat for immersed high voltage power cables, extensively used for offshore wind farms, which in turn are supposed to last for at least 20 years for their total investment to be economically viable. The Crosslinked Polyethylene (XLPE) used for the insulating layer of the cables may suffer different degradation phenomena, leading to unexpected breakdowns and rises in costs. In this work, numerical simulations have been developed to study the mechanisms by which micrometric pores inside XLPE can enlarge and coalesce (namely, water treeing) when the insulation is subjected to the intense electric field generated by hi-voltage wires. The study aim is to predict material plasticization next to voids, which is supposed to represent the onset of coalescence of neighboring pores. A microscale-level finite element coupled electro-mechanics model has been developed to describe the interactions between the intense electric fields and the subsequent Maxwell stresses in a dielectric. The roles of different influencing parameters such as distance, relative volumes, and the shape of two neighboring voids in a representative unit volume are considered. Finally, the behavior of a generic microstructure characterized by randomly distributed voids immersed in an electric field is simulated.

Förderung

  • Flow-Cam MarTERA Era-Net Project

Zitieren

APA

Miceli, M., Carvelli, V., & Drissi-Habti, M. (2023). Modelling Electro-Mechanical Behaviour of an XLPE Insulation Layer for Hi-Voltage Composite Power Cables: Effect of Voids on Onset of Coalescence. Energies, 16(12), 4620. https://doi.org/10.3390/en16124620

Vancouver

Miceli M, Carvelli V, Drissi-Habti M. Modelling Electro-Mechanical Behaviour of an XLPE Insulation Layer for Hi-Voltage Composite Power Cables: Effect of Voids on Onset of Coalescence. Energies. 2023;16(12):4620. doi:10.3390/en16124620

BibTeX
@article{Miceli2023,
  author = {Miceli, Michele and Carvelli, Valter and Drissi-Habti, Monssef},
  title = {Modelling Electro-Mechanical Behaviour of an XLPE Insulation Layer for Hi-Voltage Composite Power Cables: Effect of Voids on Onset of Coalescence},
  journal = {Energies},
  year = {2023},
  volume = {16},
  number = {12},
  pages = {4620},
  doi = {10.3390/en16124620}
}