Frequency-Support Capability Verification of Multiple VSC-HVDC Links Through Power–Energy–Duration Envelopes and Shared-Resource De-Duplication
Electronics · 23.11.2026 · 15 (23) · 5459
DOI: 10.3390/electronics15235459 ↗Kurz gefasst
Fachartikel in der Zeitschrift Electronics, online erschienen am 23.11.2026. Verfasst von Jishuo Qin und 5 weiteren Autor:innen. Die Arbeit nennt 79 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0). Gefördert von: Technical Service Project of the Headquarters of State Grid Corporation of China.
Abstract (Originalsprache)
Synchronous grids increasingly count the modulation headroom of voltage-source-converter high-voltage direct-current (VSC-HVDC) links as frequency-support capacity, although the energy behind that headroom is short-lived, shared among links or, for a link embedded in the same grid, absent altogether. This paper develops a verification that replaces rated headroom by power–energy–duration envelopes. The joint envelope of links that share sources is the minimum cut of a source–link–section flow network; the center-of-inertia identity assigns zero net energy to embedded links; and a linear program of the remote grid bounds an interconnecting link by that grid’s frequency limit. A closed-form energy demand, derived from the aggregated swing equation and the monotone governor response, gives a supply–demand criterion that proves infeasibility; and a multi-area linear program returns the reachable nadir, the allocation and the minimum additional storage. On a two-area system with four links, the rated accounting overstates the deliverable energy by 268% or more and the critical generation loss by a factor of 2.3. Among 600 random combinations, the criterion rejects 57.3% of the infeasible ones without a false rejection and the rated accounting misjudges 288. A valve-limited third-order governor lowers the critical loss from 454 to 424 MW, and at a RoCoF limit of 1.0 Hz/s, the loss carried with 95% confidence over the source states is 488 MW against 553 MW at rated wind. Detailed multi-machine models with phase-locked-loop synchronized converter stations reproduce the area nadirs within 12 mHz on the two-area system and the center-of-inertia nadir within 3.5 mHz in 15 unit-trip cases of the New England 39-bus system, and a switching-level electromagnetic-transient model of one converter station delivers 99.7% of the energy ordered within the RoCoF window.
Förderung
- Technical Service Project of the Headquarters of State Grid Corporation of China
Zitieren
APA
Qin, J., Li, F., Tao, T., Si, Y., Wang, Y., & Liang, H. (2026). Frequency-Support Capability Verification of Multiple VSC-HVDC Links Through Power–Energy–Duration Envelopes and Shared-Resource De-Duplication. Electronics, 15(23), 5459. https://doi.org/10.3390/electronics15235459
Vancouver
Qin J, Li F, Tao T, Si Y, Wang Y, Liang H. Frequency-Support Capability Verification of Multiple VSC-HVDC Links Through Power–Energy–Duration Envelopes and Shared-Resource De-Duplication. Electronics. 2026;15(23):5459. doi:10.3390/electronics15235459
BibTeX
@article{Qin2026,
author = {Qin, Jishuo and Li, Fan and Tao, Taikun and Si, Yuan and Wang, Yiran and Liang, Hanqing},
title = {Frequency-Support Capability Verification of Multiple VSC-HVDC Links Through Power–Energy–Duration Envelopes and Shared-Resource De-Duplication},
journal = {Electronics},
year = {2026},
volume = {15},
number = {23},
pages = {5459},
doi = {10.3390/electronics15235459}
}
EUVIMED