Field-Validated Induced-Voltage Testing and Power-Supply Capacity Calibration for Converter Transformer Systems Considering Parasitic Capacitance
Electronics · 11.08.2026 · 15 (16) · 3560
DOI: 10.3390/electronics15163560 ↗Kurz gefasst
Fachartikel in der Zeitschrift Electronics, online erschienen am 11.08.2026. Verfasst von Lujia Wang und 5 weiteren Autor:innen. Die Arbeit nennt 21 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0). Gefördert von: Technical Service Project of State Grid Anhui Electric Power Research Institute.
Abstract (Originalsprache)
Field voltage testing after the maintenance of large converter transformers requires high-voltage response verification while preserving the restored equipment boundary. However, conventional direct voltage application on the grid side usually requires the disconnection of high-voltage leads and auxiliary devices, which may alter the original electrical boundary and increase field disturbance. To address this issue, this study develops an integrated framework with three core contributions: a minimal-lead-disconnection induced-voltage testing topology, a boundary-specific engineering-equivalent parasitic-capacitance model, and a terminal-referred phasor-based power-supply capacity-calibration method. Under the proposed testing topology, single-phase power-frequency excitation is applied on the valve side, and the induced-voltage response is established at the grid-side bushings while some of the restored auxiliary-equipment connections are retained. Considering the parasitic capacitance introduced by valve towers, tubular busbars, grading fittings, and grid-side auxiliary devices under the minimal-lead-disconnection boundary, an engineering equivalent model for extracting the valve-side stray capacitance is developed based on quasi-static electric field theory, geometric-envelope dimensional reduction, and conformal-mapping-based edge correction. The grid-side equivalent capacitance is further obtained using equipment parameters. On this basis, the induced-voltage distribution under the interconnection of multiple converter transformers is analyzed, and a power-supply capacity-calibration method considering the phasor relationship between inductive excitation current and capacitive current is established. Pre-test calculations yield a valve-side stray capacitance of 0.96 nF and a grid-side equivalent capacitance of 1.27 nF. When the grid-side induced voltage of phase C reaches 9.90 kV, the induced voltages of phases A and B are 4.56 kV and 5.14 kV, respectively, while the apparent power calculated from the field-measured RMS voltage and current is 1.34 kVA. The results verify the effectiveness of the proposed method for low-disturbance field testing and portable test-power-supply configuration.
Förderung
- Technical Service Project of State Grid Anhui Electric Power Research Institute
Zitieren
APA
Wang, L., Yang, L., Zhang, Y., Xie, Y., Yang, D., & Yang, H. (2026). Field-Validated Induced-Voltage Testing and Power-Supply Capacity Calibration for Converter Transformer Systems Considering Parasitic Capacitance. Electronics, 15(16), 3560. https://doi.org/10.3390/electronics15163560
Vancouver
Wang L, Yang L, Zhang Y, Xie Y, Yang D, Yang H. Field-Validated Induced-Voltage Testing and Power-Supply Capacity Calibration for Converter Transformer Systems Considering Parasitic Capacitance. Electronics. 2026;15(16):3560. doi:10.3390/electronics15163560
BibTeX
@article{Wang2026,
author = {Wang, Lujia and Yang, Ling and Zhang, Yongqi and Xie, Yiming and Yang, Dingqian and Yang, Haitao},
title = {Field-Validated Induced-Voltage Testing and Power-Supply Capacity Calibration for Converter Transformer Systems Considering Parasitic Capacitance},
journal = {Electronics},
year = {2026},
volume = {15},
number = {16},
pages = {3560},
doi = {10.3390/electronics15163560}
}
EUVIMED