EUVIMEDEUVIMED entdecken
Open Access · CC BY 4.0

Stability Analysis and Frequency-Segmented Active Damping Method of Hybrid Grid-Following and Grid-Forming Inverter System Under Power Variations

Yuchen Tang, Yi Lin, Rong Ye, Jiabao Li, Jinjie Lin, Fenghuang Cai, Rui Zhu

Electronics · 21.07.2026 · 15 (14) · 3209

DOI: 10.3390/electronics15143209 ↗

Kurz gefasst

Fachartikel in der Zeitschrift Electronics, online erschienen am 21.07.2026. Verfasst von Yuchen Tang und 6 weiteren Autor:innen. Die Arbeit nennt 30 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0). Gefördert von: State Grid Fujian Electric Power Co. Ltd..

AbstractBibliografische AngabenZitierenVerwandte Studien

Abstract (Originalsprache)

Hybrid systems integrating grid-following (GFL) and grid-forming (GFM) inverters are increasingly deployed in renewable-energy-dominated power systems. However, impedance coupling between the two inverter types may induce low-frequency oscillations and high-frequency resonances, particularly under weak-grid conditions and varying power injections. This paper clarifies the stability mechanism of a hybrid GFL/GFM inverter system and develops a frequency-segmented active damping strategy. Small-signal impedance models are first derived for the GFL inverter, the GFM inverter, and the overall hybrid system, incorporating the control loops, digital delay, LC filters, interconnection branch impedances, and external grid impedance. Impedance decomposition, Bode plots, and Nyquist criteria are then employed to quantify the influence of power operating points and grid strength on system stability. The results indicate that increasing the GFL inverter output power weakens the stability margins in both low- and high-frequency ranges, whereas variations in the GFM inverter output power provide only limited impedance reshaping in the targeted oscillation bands. On this basis, a low-frequency damping loop is designed on the GFM inverter side, while a high-frequency damping loop based on capacitor-current feedback is implemented on the GFL inverter side. Simulation results confirm that the proposed strategy suppresses low-frequency oscillations and high-frequency harmonic components, maintains stable operation in the hybrid system under high GFL power injection, and reduces the THD of the PCC current from 14.52% to 0.62%.

Förderung

  • State Grid Fujian Electric Power Co. Ltd.

Zitieren

APA

Tang, Y., Lin, Y., Ye, R., Li, J., Lin, J., Cai, F., & Zhu, R. (2026). Stability Analysis and Frequency-Segmented Active Damping Method of Hybrid Grid-Following and Grid-Forming Inverter System Under Power Variations. Electronics, 15(14), 3209. https://doi.org/10.3390/electronics15143209

Vancouver

Tang Y, Lin Y, Ye R, Li J, Lin J, Cai F, et al. Stability Analysis and Frequency-Segmented Active Damping Method of Hybrid Grid-Following and Grid-Forming Inverter System Under Power Variations. Electronics. 2026;15(14):3209. doi:10.3390/electronics15143209

BibTeX
@article{Tang2026,
  author = {Tang, Yuchen and Lin, Yi and Ye, Rong and Li, Jiabao and Lin, Jinjie and Cai, Fenghuang and Zhu, Rui},
  title = {Stability Analysis and Frequency-Segmented Active Damping Method of Hybrid Grid-Following and Grid-Forming Inverter System Under Power Variations},
  journal = {Electronics},
  year = {2026},
  volume = {15},
  number = {14},
  pages = {3209},
  doi = {10.3390/electronics15143209}
}
Kostenlos starten →