Direct Internal Voltage Control-Based Fault Current-Limiting Control Strategy for Grid-Forming Converters with LCL Filter

Han Yan, Jianhua Wang, Xiaokuan Jin, Ziyi Xia, Jianfeng Zhao

Electronics · 28.05.2026 · 15 (11) · 2341

DOI: 10.3390/electronics15112341 ↗

Kurz gefasst

Fachartikel in der Zeitschrift Electronics, online erschienen am 28.05.2026. Verfasst von Han Yan und 4 weiteren Autor:innen. Die Arbeit nennt 31 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0). Gefördert von: Scientific and Technological Achievements Transformation Project of Jiangsu Province.

AbstractBibliografische AngabenZitierenVerwandte Studien

Abstract (Originalsprache)

Grid-forming (GFM) converters enhance power system stability by emulating synchronous generators, but their limited overcurrent capability under grid faults poses a critical challenge to transient stability. Existing current-limiting methods often force a trade-off between fault current suppression and voltage support. To address this, a direct internal voltage control (DIVC)-based fault current-limiting strategy is proposed. The DIVC framework eliminates inner control loops and directly regulates the internal voltage amplitude and phase by leveraging measurements at the point of common coupling (PCC) and the converter output, enabling fast, accurate current control within a virtual synchronous generator (VSG) architecture. Under mild faults, the strategy prioritizes maintaining the terminal voltage to preserve voltage source behavior; under severe faults, it smoothly transitions to a current-limiting mode that preserves the terminal voltage phase angle to support transient synchronization. The scheme incorporates compensation-enabling criteria, dual-mode amplitude/phase compensation, and power reference modification. Experimental results under an 80% voltage sag demonstrate that the proposed method limits the transient current peak to 1.1 p.u. and ensures oscillation-free recovery within 0.1 s, significantly outperforming conventional current saturation and virtual impedance techniques. The proposed approach also exhibits strong current-limiting capability under unbalanced faults.

Förderung

  • Scientific and Technological Achievements Transformation Project of Jiangsu Province

Zitieren

APA

Yan, H., Wang, J., Jin, X., Xia, Z., & Zhao, J. (2026). Direct Internal Voltage Control-Based Fault Current-Limiting Control Strategy for Grid-Forming Converters with LCL Filter. Electronics, 15(11), 2341. https://doi.org/10.3390/electronics15112341

Vancouver

Yan H, Wang J, Jin X, Xia Z, Zhao J. Direct Internal Voltage Control-Based Fault Current-Limiting Control Strategy for Grid-Forming Converters with LCL Filter. Electronics. 2026;15(11):2341. doi:10.3390/electronics15112341

BibTeX
@article{Yan2026,
  author = {Yan, Han and Wang, Jianhua and Jin, Xiaokuan and Xia, Ziyi and Zhao, Jianfeng},
  title = {Direct Internal Voltage Control-Based Fault Current-Limiting Control Strategy for Grid-Forming Converters with LCL Filter},
  journal = {Electronics},
  year = {2026},
  volume = {15},
  number = {11},
  pages = {2341},
  doi = {10.3390/electronics15112341}
}
Kostenlos starten →