EUVIMEDEUVIMED entdecken
Open Access · CC BY 4.0

Accurate Fault Location Method Based on Time-Domain Information Estimation for Medium-Voltage Distribution Network

Guanqun Sun, Rusi Chen, Zheyu Han, Haiguang Liu, Meiyuan Liu, Ke Zhang, Chaozheng Xu, Yikai Wang

Electronics · 22.11.2023 · 12 (23) · 4733

DOI: 10.3390/electronics12234733 ↗

Kurz gefasst

Fachartikel in der Zeitschrift Electronics, online erschienen am 22.11.2023. Verfasst von Guanqun Sun und 7 weiteren Autor:innen. Die Arbeit wurde bisher 6-mal zitiert (Crossref) und nennt 29 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0). Gefördert von: National Natural Science Foundation of China.

AbstractBibliografische AngabenZitierenVerwandte Studien

Abstract (Originalsprache)

The sampling rate of the wide-area synchronous phasor measuring device (D-PMU) in the distribution network is insufficient, and the localization sensitivity of the traditional localization method based on the time-domain Bergeron equation in the distribution network is insufficient. In this paper, an accurate location method of the distribution line grounding fault based on the time-domain’ synchronous information calculation is proposed to solve the problem of limited location accuracy caused by a low sampling rate and the insufficient sensitivity of traditional methods. The method preprocesses the measurement data through low-frequency time-domain signal reconstruction and cubic spline interpolation. The fault current’s different location criterion is constructed by using the voltage and current constraints at the fault point. By calculating the fault current difference at a limited number of calculated points, the accurate fault location under a low sampling rate is realized, which is beneficial to the rapid maintenance of faults and the shortening of the power outage time.

Förderung

  • National Natural Science Foundation of China

Zitieren

APA

Sun, G., Chen, R., Han, Z., Liu, H., Liu, M., Zhang, K., Xu, C., & Wang, Y. (2023). Accurate Fault Location Method Based on Time-Domain Information Estimation for Medium-Voltage Distribution Network. Electronics, 12(23), 4733. https://doi.org/10.3390/electronics12234733

Vancouver

Sun G, Chen R, Han Z, Liu H, Liu M, Zhang K, et al. Accurate Fault Location Method Based on Time-Domain Information Estimation for Medium-Voltage Distribution Network. Electronics. 2023;12(23):4733. doi:10.3390/electronics12234733

BibTeX
@article{Sun2023,
  author = {Sun, Guanqun and Chen, Rusi and Han, Zheyu and Liu, Haiguang and Liu, Meiyuan and Zhang, Ke and Xu, Chaozheng and Wang, Yikai},
  title = {Accurate Fault Location Method Based on Time-Domain Information Estimation for Medium-Voltage Distribution Network},
  journal = {Electronics},
  year = {2023},
  volume = {12},
  number = {23},
  pages = {4733},
  doi = {10.3390/electronics12234733}
}
Kostenlos starten →