Hybrid Active Damping for LCL-Filtered Inverters Under Weak-Grid Conditions Using Dual-Current Feedback and Capacitor-Voltage Feedforward
Electricity · 19.10.2026 · 7 (4) · 124
DOI: 10.3390/electricity7040124 ↗Kurz gefasst
Fachartikel in der Zeitschrift Electricity, online erschienen am 19.10.2026. Verfasst von Changxing Sun und 5 weiteren Autor:innen. Die Arbeit nennt 38 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0). Gefördert von: Henan Institute of Technology.
Abstract (Originalsprache)
Variations in grid inductance shift the resonance characteristics of inductor-capacitor-inductor (LCL) filters and can reduce the stability margins of digitally controlled grid-connected inverters. This paper proposes a hybrid active-damping strategy that combines grid-current feedback for current regulation, inverter-current feedback for active damping, and capacitor-voltage feedforward to modify the closed-loop dynamics. An open-loop model incorporating the LCL network, equivalent grid inductance, and digital control delay is derived for small-signal stability analysis. Resonance damping is evaluated through frequency-domain analysis and comparative simulations with grid-current-only control. Additional offline simulations examine current-reference tracking and operation under background grid-voltage harmonics, while real-time hardware-in-the-loop (HIL) tests evaluate steady-state current regulation and harmonic performance. Frequency-domain analysis shows suppressed resonance-related gain amplification and positive phase margins at the three evaluated grid-inductance values. Reference tracking is demonstrated in offline simulations, which also show maintained current regulation under the specified grid-voltage harmonics. In the steady-state HIL tests, three-phase grid currents remain bounded and periodic without pronounced resonance-induced oscillations. Across the three HIL cases, individual harmonics from the second to the fortieth order remain below 1% of the fundamental component, and grid-current total harmonic distortion remains below 1.2%. These findings demonstrate effective resonance damping and grid-current regulation under the investigated grid-inductance conditions.
Förderung
- Henan Institute of Technology
Zitieren
APA
Sun, C., Li, Y., Chen, X., Qi, S., Guo, B., & Li, Q. (2026). Hybrid Active Damping for LCL-Filtered Inverters Under Weak-Grid Conditions Using Dual-Current Feedback and Capacitor-Voltage Feedforward. Electricity, 7(4), 124. https://doi.org/10.3390/electricity7040124
Vancouver
Sun C, Li Y, Chen X, Qi S, Guo B, Li Q. Hybrid Active Damping for LCL-Filtered Inverters Under Weak-Grid Conditions Using Dual-Current Feedback and Capacitor-Voltage Feedforward. Electricity. 2026;7(4):124. doi:10.3390/electricity7040124
BibTeX
@article{Sun2026,
author = {Sun, Changxing and Li, Yixiang and Chen, Xuyang and Qi, Shancheng and Guo, Beibei and Li, Qiqi},
title = {Hybrid Active Damping for LCL-Filtered Inverters Under Weak-Grid Conditions Using Dual-Current Feedback and Capacitor-Voltage Feedforward},
journal = {Electricity},
year = {2026},
volume = {7},
number = {4},
pages = {124},
doi = {10.3390/electricity7040124}
}