EUVIMEDEUVIMED entdecken
Open Access · CC BY 4.0

Modified Negative-Sequence Overcurrent Protection for Operation Under Load Asymmetry Conditions

Denis Fedosov, Iliya Iliev, Hristo Beloev, Konstantin Suslov, Anton Suslov, Ilia Shuspanov, Ivan Beloev

Electricity · 16.07.2026 · 7 (3) · 71

DOI: 10.3390/electricity7030071 ↗

Kurz gefasst

Fachartikel in der Zeitschrift Electricity, online erschienen am 16.07.2026. Verfasst von Denis Fedosov und 6 weiteren Autor:innen. Die Arbeit nennt 31 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0). Gefördert von: European Union.

AbstractBibliografische AngabenZitierenVerwandte Studien

Abstract (Originalsprache)

This article examines the performance of negative-sequence overcurrent protection during short circuits in the presence of current asymmetry caused by single-phase loads, such as those encountered in AC railway traction systems. The impact of unbalanced loads on the generation of negative-sequence currents is analyzed using field test data and a mathematical model. Various operating modes of an electric power network under unbalanced loading conditions are simulated in MATLAB Simulink R2015a. It is shown that under significant load asymmetry, negative-sequence currents can reach magnitudes comparable to those of short-circuit currents, thereby increasing the risk of false protection operation. To address this issue, a modified negative-sequence overcurrent protection scheme is proposed that ensures both sensitivity and selectivity. The modification is based on analyzing the ratio of negative-sequence to positive-sequence current phasors and monitoring the rate of change of the negative-sequence current. A faulted phase selector is also incorporated into the protection scheme. Simulation results confirm the effectiveness of the modified protection in reliably identifying unsymmetrical short circuits under varying unbalanced load conditions, including remote faults with high fault resistance.

Förderung

  • European Union

Zitieren

APA

Fedosov, D., Iliev, I., Beloev, H., Suslov, K., Suslov, A., Shuspanov, I., & Beloev, I. (2026). Modified Negative-Sequence Overcurrent Protection for Operation Under Load Asymmetry Conditions. Electricity, 7(3), 71. https://doi.org/10.3390/electricity7030071

Vancouver

Fedosov D, Iliev I, Beloev H, Suslov K, Suslov A, Shuspanov I, et al. Modified Negative-Sequence Overcurrent Protection for Operation Under Load Asymmetry Conditions. Electricity. 2026;7(3):71. doi:10.3390/electricity7030071

BibTeX
@article{Fedosov2026,
  author = {Fedosov, Denis and Iliev, Iliya and Beloev, Hristo and Suslov, Konstantin and Suslov, Anton and Shuspanov, Ilia and Beloev, Ivan},
  title = {Modified Negative-Sequence Overcurrent Protection for Operation Under Load Asymmetry Conditions},
  journal = {Electricity},
  year = {2026},
  volume = {7},
  number = {3},
  pages = {71},
  doi = {10.3390/electricity7030071}
}
Kostenlos starten →