EUVIMEDEUVIMED entdecken
Open Access · CC BY 4.0

Comparative Case Study of Balancing Strategies in a Single-Pipe Heating System

Andrius Timofejevas, Kęstutis Valančius

Buildings · 18.11.2026 · 16 (22) · 4592

DOI: 10.3390/buildings16224592 ↗

Kurz gefasst

Fachartikel in der Zeitschrift Buildings, online erschienen am 18.11.2026. Verfasst von Andrius Timofejevas und 1 weiteren Autor:innen. Die Arbeit nennt 30 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0).

AbstractBibliografische AngabenZitierenVerwandte Studien

Abstract (Originalsprache)

Hydraulic imbalance in single-pipe heating systems remains a significant issue in older multi-apartment buildings, often resulting in uneven heat distribution, reduced occupant comfort, and increased energy consumption. This case study investigates the influence of different balancing and control strategies on the thermal and hydraulic performance of a renovated single-pipe heating system in a residential building in Ukmergė, Lithuania. Five system configurations were analyzed: (1) an unbalanced system without thermostats or balancing valves, (2) a system with thermostatic radiator valves only, (3) a system with balancing valves and thermostats, (4) a system with fully closed bypasses and without balancing valves, and (5) a system with balancing valves, thermostats, and return-temperature control. The analysis was performed using Danfoss SET 7.0 software (version 7.0; Danfoss A/S, Nordborg, Denmark) and Wilo Select software (version 5.0; WILO SE, Dortmund, Germany) tools to evaluate flow distribution, return-temperature behavior and circulation pump energy consumption, under different operating conditions. The investigated building consists of 30 apartments with a total heated area of 1758.42 m2. The calculations indicate a more uniform riser return-temperature distribution under the prescribed riser-specific return-temperature limits. Scenario 5, combining thermostatic radiator valves, automatic balancing and assumed return-temperature-based flow limitation, yielded an estimated annual pump electricity consumption of 344.05 kWh/year based on the supplied Wilo operating points. This is 37.7% lower than Scenario 3 (552 kWh/year), but approximately 1.5% higher than the uncontrolled Scenario 1 (339 kWh/year). The return-temperature results reflect imposed control limits rather than independently validated controller performance. Actual radiator heat delivery, indoor thermal comfort and operational savings were not verified. The findings illustrate the potential relevance of hydraulic balancing and return-temperature management when assessing retrofit options for existing single-pipe heating systems. They provide comparative engineering insights rather than experimentally validated estimates of building or district-heating-network energy savings.

Zitieren

APA

Timofejevas, A., & Valančius, K. (2026). Comparative Case Study of Balancing Strategies in a Single-Pipe Heating System. Buildings, 16(22), 4592. https://doi.org/10.3390/buildings16224592

Vancouver

Timofejevas A, Valančius K. Comparative Case Study of Balancing Strategies in a Single-Pipe Heating System. Buildings. 2026;16(22):4592. doi:10.3390/buildings16224592

BibTeX
@article{Timofejevas2026,
  author = {Timofejevas, Andrius and Valančius, Kęstutis},
  title = {Comparative Case Study of Balancing Strategies in a Single-Pipe Heating System},
  journal = {Buildings},
  year = {2026},
  volume = {16},
  number = {22},
  pages = {4592},
  doi = {10.3390/buildings16224592}
}
Kostenlos starten →