Fachartikel in der Zeitschrift Buildings, online erschienen am 16.11.2026. Verfasst von Rossana Laera und 1 weiteren Autor:innen. Die Arbeit nennt 51 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0).
Abstract (Originalsprache)
Thermally activated building systems (TABS) shift energy demand away from grid peaks, yet retrofitted buildings often retain heterogeneous slabs, unlike the homogeneous slabs assumed in most studies. This study aims (i) to document compliance with the LEED v5 Grid Harmonization credit at Apolonio Morales 29, an office building in Madrid certified in 2025 with the highest score worldwide for this version; and (ii) to compare six slab typologies through adiabatic simulations with fixed operating parameters. Measurements show winter thermal peak-demand reductions of up to 90%, with a median 15 h reduced-demand period on 126 of 129 winter working days; simulated behavior was checked for consistency with these data. Composition mainly determined heat distribution between floors (inter-floor air-temperature gap of 1.5–1.6 °C in heterogeneous versus ≈ 0.7 °C in homogeneous slabs), whereas pipe depth and intervening mass determined accumulated demand (up to +82%). Heterogeneous slabs, like the case study, suit directional heating and a single nightly charging window; homogeneous slabs can serve two floors from one circuit at higher demand. Sensitivity analyses show relative demand and temperature patterns persist when infiltration or supply temperature change, whereas absolute demand and cycle durations do not, supporting relative comparisons for design and control.
Zitieren
APA
Laera, R., & Pérez, I. M. (2026). Thermal Energy Storage and Peak-Demand Reduction in a Retrofitted TABS Office Building: Measured Performance and a Simulation-Based Comparison of Slab Typologies Differing in Composition and Pipe Position. Buildings, 16(22), 4565. https://doi.org/10.3390/buildings16224565
Vancouver
Laera R, Pérez IM. Thermal Energy Storage and Peak-Demand Reduction in a Retrofitted TABS Office Building: Measured Performance and a Simulation-Based Comparison of Slab Typologies Differing in Composition and Pipe Position. Buildings. 2026;16(22):4565. doi:10.3390/buildings16224565
BibTeX
@article{Laera2026,
author = {Laera, Rossana and Pérez, Inmaculada Martínez},
title = {Thermal Energy Storage and Peak-Demand Reduction in a Retrofitted TABS Office Building: Measured Performance and a Simulation-Based Comparison of Slab Typologies Differing in Composition and Pipe Position},
journal = {Buildings},
year = {2026},
volume = {16},
number = {22},
pages = {4565},
doi = {10.3390/buildings16224565}
}