Fachartikel in der Zeitschrift Buildings, online erschienen am 04.11.2026. Verfasst von Alphonse Bouda und 4 weiteren Autor:innen. Die Arbeit nennt 54 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0). Gefördert von: Regional Scholarship and Innovation Fund.

AbstractBibliografische AngabenZitierenVerwandte Studien

Abstract (Originalsprache)

Mixed-mode offices in sub-Saharan hot semi-arid climates face growing thermal stress, yet long-term evidence remains scarce. This study addresses this gap via a stress-test framework (RCP8.5) applied to a compressed earth bricks office in Ouagadougou, Burkina Faso. A calibrated DesignBuilder/EnergyPlus model evaluated four strategies—free-running (FR), natural ventilation (NV), mixed-mode (MM), and fully air-conditioned (AC)—under current (2023) and future horizons (2030, 2060, 2090). Thermal comfort was assessed using ASHRAE-55 adaptive (80%) for FR, NV, and MM, and PMV-PPD for AC. Results show that outdoor temperatures rise by +0.73 °C (2030), +2.6 °C (2060), and +4.71 °C (2090). Passive-only strategies maintain zero energy but show severely growing discomfort. Under AC27, energy demand reaches 282.6 kWh/m2·year by 2090. MM27 reduces discomfort from 9.8% (2023) to 28.1% (2090) while consuming about half the energy of full AC (124.7 kWh/m2·year by 2090), corresponding to an AC/MM energy ratio of 1.9 to 2.3 times. The share of occupied hours with windows open falls below 50% already in 2023, and below 30% between 2030 and 2060—a transition toward cooling-dominated behaviour not previously quantified for the Sudano-Sahelian zone. These findings support mixed-mode as a climate-contingent strategy for sub-Saharan offices, though validation across multiple zones and typologies is needed.

Förderung

  • Regional Scholarship and Innovation Fund

Zitieren

APA

Bouda, A., Hema, C., Messan, A., Daho, T., & Attia, S. (2026). Adaptive Thermal Comfort Assessment in Mixed-Mode Office Buildings Under Current and Future Sub-Saharan Tropical Hot and Dry Climate Scenarios. Buildings, 16(21), 4410. https://doi.org/10.3390/buildings16214410

Vancouver

Bouda A, Hema C, Messan A, Daho T, Attia S. Adaptive Thermal Comfort Assessment in Mixed-Mode Office Buildings Under Current and Future Sub-Saharan Tropical Hot and Dry Climate Scenarios. Buildings. 2026;16(21):4410. doi:10.3390/buildings16214410

BibTeX
@article{Bouda2026,
  author = {Bouda, Alphonse and Hema, Césaire and Messan, Adamah and Daho, Tizane and Attia, Shady},
  title = {Adaptive Thermal Comfort Assessment in Mixed-Mode Office Buildings Under Current and Future Sub-Saharan Tropical Hot and Dry Climate Scenarios},
  journal = {Buildings},
  year = {2026},
  volume = {16},
  number = {21},
  pages = {4410},
  doi = {10.3390/buildings16214410}
}
Kostenlos starten →