Multi-Scale Computational Fluid Dynamics Investigation of Ventilation-Controlled and Gravity-Controlled Respiratory Aerosol Transport in an Office Environment: Implications for Heating, Ventilation, and Air Conditioning Design and Airborne Infection Mitigation

Mahmoud Ahmed Fouad, Mostafa Abdelhamid Rizk, Abdullah Alhajry, Mostafa Shawky Abdelmoez

Buildings · 27.10.2026 · 16 (21) · 4297

DOI: 10.3390/buildings16214297 ↗

Kurz gefasst

Fachartikel in der Zeitschrift Buildings, online erschienen am 27.10.2026. Verfasst von Mahmoud Ahmed Fouad und 3 weiteren Autor:innen. Die Arbeit nennt 50 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0).

AbstractBibliografische AngabenZitierenVerwandte Studien

Abstract (Originalsprache)

This study presents a comprehensive transient Computational Fluid Dynamics–Discrete Phase Model (CFD-DPM) investigation of aerosol and droplet transport in an air-conditioned office containing one infected occupant and three susceptible occupants. The transition from ventilation-controlled to gravity-dominated transport of respiratory aerosols in office settings remains poorly characterized. Continuous emission over 300 s was simulated for particle diameters of 1, 5, 10, and 50 µm. The continuous airflow field was resolved using the pressure-based solver, energy equation, and Shear Stress Transport k-ω turbulence model, validated against experimental temperature and relative humidity data with mean absolute errors of 0.59 °C and 1.26% relative humidity, respectively. The airflow model was validated against temperature and relative humidity data only; the discrete-phase predictions were not validated directly against experimental aerosol data. A critical finding is the identification of three distinct transport regimes: Regime I (1–5 µm), characterized by ventilation-dominated behavior with strong airflow coupling, approximately 50% outlet removal, and 38–39% airborne fraction at 300 s; Regime II (10 µm), representing a mixed-transition zone where gravitational effects begin to compete with aerodynamic forces; and Regime III (50 µm), dominated by gravitational settling with 93% deposition and only 1.6% outlet removal at 300 s. The critical transition diameter between ventilation-controlled and gravity-dominated transport was estimated to be approximately 20–30 µm based on interpolation between the 10 µm and 50 µm cases and dimensionless analysis; this estimate requires further validation with intermediate particle sizes. Dimensionless analysis revealed that particles with Stokes numbers below 0.1 remain strongly coupled to the airflow, while those exceeding 1.0 exhibit ballistic trajectories dominated by inertia and gravity. Outlet-2 consistently served as the dominant removal path for all particle sizes, confirming an asymmetric ventilation transport route attributable to the supply jet trajectory and recirculation patterns. Human 2 received the highest body-deposition fraction for aerosol-sized particles (0.287% for 1 µm, 0.123% for 5 and 10 µm at 300 s), identifying this location as a critical exposure zone. For 50 µm droplets, susceptible occupant deposition was negligible (

Zitieren

APA

Fouad, M. A., Rizk, M. A., Alhajry, A., & Abdelmoez, M. S. (2026). Multi-Scale Computational Fluid Dynamics Investigation of Ventilation-Controlled and Gravity-Controlled Respiratory Aerosol Transport in an Office Environment: Implications for Heating, Ventilation, and Air Conditioning Design and Airborne Infection Mitigation. Buildings, 16(21), 4297. https://doi.org/10.3390/buildings16214297

Vancouver

Fouad MA, Rizk MA, Alhajry A, Abdelmoez MS. Multi-Scale Computational Fluid Dynamics Investigation of Ventilation-Controlled and Gravity-Controlled Respiratory Aerosol Transport in an Office Environment: Implications for Heating, Ventilation, and Air Conditioning Design and Airborne Infection Mitigation. Buildings. 2026;16(21):4297. doi:10.3390/buildings16214297

BibTeX
@article{Fouad2026,
  author = {Fouad, Mahmoud Ahmed and Rizk, Mostafa Abdelhamid and Alhajry, Abdullah and Abdelmoez, Mostafa Shawky},
  title = {Multi-Scale Computational Fluid Dynamics Investigation of Ventilation-Controlled and Gravity-Controlled Respiratory Aerosol Transport in an Office Environment: Implications for Heating, Ventilation, and Air Conditioning Design and Airborne Infection Mitigation},
  journal = {Buildings},
  year = {2026},
  volume = {16},
  number = {21},
  pages = {4297},
  doi = {10.3390/buildings16214297}
}