Characterizing Energy-Saving Levels in Green Remodeling Projects for Public Buildings: A Case-Based Analysis of Energy Composition and Retrofit Measures

Jihoon Jang, Hosang Ahn, Jae Sik Kang, Suin Lee

Buildings · 16.07.2026 · 16 (14) · 2829

DOI: 10.3390/buildings16142829 ↗

Kurz gefasst

Fachartikel in der Zeitschrift Buildings, online erschienen am 16.07.2026. Verfasst von Jihoon Jang und 3 weiteren Autor:innen. Die Arbeit nennt 39 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0). Gefördert von: Ministry of Land, Infrastructure and Transport.

AbstractBibliografische AngabenZitierenVerwandte Studien

Abstract (Originalsprache)

Green remodeling projects for public buildings in South Korea aim to improve the energy performance of aging facilities, with a policy target of achieving at least 30% energy savings. Because the 30% saving rate functions as a key policy benchmark, it is necessary to identify why some projects achieve higher savings while others remain below the target. This requires a comparative analysis of energy-saving levels in relation to baseline energy-use composition and retrofit measure applications. This study analyzes the 1954 preliminary investigation and ECO2-OD-based assessment cases of public building green remodeling projects to examine energy-saving levels, baseline energy-use composition, end-use contributions, and retrofit measure applications. Pre- and post-retrofit primary energy demand for heating, cooling, domestic hot water, and lighting were used to calculate energy-saving rates. Based on the 30% policy target, the cases were classified into Low-saving, Target-achieving, High-saving, and Very-high-saving levels. The average energy-saving rate was 36.02%, but 39.61% of cases remained below the 30% target. Higher-saving groups showed greater baseline heating energy shares, increasing from 53.38% in the Low-saving group to 66.18% in the Very-high-saving group, suggesting an association between pre-retrofit energy-use structure and predicted retrofit potential under the ECO2-OD assessment framework. Heating was also the dominant contributor to total savings, with its contribution rising from 17.07 to 44.94 percentage points. Higher-saving cases tended to involve more comprehensive retrofit packages combining envelope, system, and lighting improvements. These findings suggest that energy-saving targets and retrofit strategies should consider baseline end-use energy composition and establish differentiated saving targets according to building characteristics, rather than relying only on uniform policy targets and average project performance.

Förderung

  • Ministry of Land, Infrastructure and Transport

Zitieren

APA

Jang, J., Ahn, H., Kang, J. S., & Lee, S. (2026). Characterizing Energy-Saving Levels in Green Remodeling Projects for Public Buildings: A Case-Based Analysis of Energy Composition and Retrofit Measures. Buildings, 16(14), 2829. https://doi.org/10.3390/buildings16142829

Vancouver

Jang J, Ahn H, Kang JS, Lee S. Characterizing Energy-Saving Levels in Green Remodeling Projects for Public Buildings: A Case-Based Analysis of Energy Composition and Retrofit Measures. Buildings. 2026;16(14):2829. doi:10.3390/buildings16142829

BibTeX
@article{Jang2026,
  author = {Jang, Jihoon and Ahn, Hosang and Kang, Jae Sik and Lee, Suin},
  title = {Characterizing Energy-Saving Levels in Green Remodeling Projects for Public Buildings: A Case-Based Analysis of Energy Composition and Retrofit Measures},
  journal = {Buildings},
  year = {2026},
  volume = {16},
  number = {14},
  pages = {2829},
  doi = {10.3390/buildings16142829}
}
Kostenlos starten →