Study on Operating Strategies Coupling Floor-Cooling and Cold Storage in Thermal Active System

Haiying Wang, Yongcheng Wang, Chenxi Dong, Lingyu Chang, Andi Yu, Kefei Gong, Xiao Fang, Songtao Hu

Buildings · 03.07.2026 · 16 (13) · 2654

DOI: 10.3390/buildings16132654 ↗

Kurz gefasst

Fachartikel in der Zeitschrift Buildings, online erschienen am 03.07.2026. Verfasst von Haiying Wang und 7 weiteren Autor:innen. Die Arbeit nennt 32 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0). Gefördert von: Shandong Provincial Natural Science Foundation Project.

AbstractBibliografische AngabenZitierenVerwandte Studien

Abstract (Originalsprache)

To explore the optimized operating strategies coupling floor cooling with cold storage for thermal active systems (TABSs), effects of operating time on indoor thermal environment, cold storage capacity, energy use and running cost were studied. Simulations were conducted based on an actual office building equipped with floor cooling. To take full advantage of the TABS and off-peak electricity, four operating cases with nighttime floor cold storage were proposed, namely C1 (2:00–8:00), which operated only during the off-peak hours, C2 (2:00–10:00), C3 (2:00–12:00), and C4 (2:00–14:00), which operated during the off-peak and flat hours. A simulation case of C0 operating during daytime (7:00–17:00) was also proposed. Simulation results show that the C1 and C2 conditions with shorter operating hours result in higher indoor temperatures, which cannot ensure indoor thermal comfort. The PMV index in C3 and C4 conditions can be kept between −1 and 1, which meets the thermal comfort demand of Grade II. Considering that the operating duration of C3 is the same as the occupied hours, the cold storage capacity, cooling loss, cooling supply and release process, etc., of this case are further analyzed based on data of a typical day. The floor and ceiling slabs store most of the cooling energy (72.7%) during the night; inner walls also store part of the cooling energy (23.3%) and cooling loss during cold storage accounts for approximately 3.1%. During working hours, the cooling energy released is lower than the cooling load, which makes indoor temperatures increase continuously. Compared with case C0, case C3 has same power use while saving 2.8% of running costs. Case C4 provides a higher level of thermal comfort, while saving 0.9% of costs with a 1.5% increment in electricity use. This study provides detailed data about cold storage strategies coupling with floor cooling in TABS, which can be used to save running cost.

Förderung

  • Shandong Provincial Natural Science Foundation Project

Zitieren

APA

Wang, H., Wang, Y., Dong, C., Chang, L., Yu, A., Gong, K., Fang, X., & Hu, S. (2026). Study on Operating Strategies Coupling Floor-Cooling and Cold Storage in Thermal Active System. Buildings, 16(13), 2654. https://doi.org/10.3390/buildings16132654

Vancouver

Wang H, Wang Y, Dong C, Chang L, Yu A, Gong K, et al. Study on Operating Strategies Coupling Floor-Cooling and Cold Storage in Thermal Active System. Buildings. 2026;16(13):2654. doi:10.3390/buildings16132654

BibTeX
@article{Wang2026,
  author = {Wang, Haiying and Wang, Yongcheng and Dong, Chenxi and Chang, Lingyu and Yu, Andi and Gong, Kefei and Fang, Xiao and Hu, Songtao},
  title = {Study on Operating Strategies Coupling Floor-Cooling and Cold Storage in Thermal Active System},
  journal = {Buildings},
  year = {2026},
  volume = {16},
  number = {13},
  pages = {2654},
  doi = {10.3390/buildings16132654}
}
Kostenlos starten →