Abstract (Originalsprache)

To improve the indoor thermal comfort of embedded atriums and corridors in office buildings during summer, this study aims to optimize air conditioning airflow organization in atriums using computational fluid dynamics (CFD) simulations. Field measurements were carried out to collect air parameters, which were subsequently used to validate the established CFD model. Taking a six-story office building in Xi’an as the research subject and stratified air conditioning as the baseline case, this study investigated the effects of air inlet layout, air inlet type, and air volume distribution on the indoor thermal environment. The results revealed significant vertical temperature stratification within the atrium, with average temperatures ranging from 23.5 °C to 46.1 °C. Based on comparative analysis of multiple optimization scenarios, the following conclusions are drawn: adopting swirl diffusers in the corridors with an air inlet quantity ratio of 1:1:1:1:2 from the first to fifth floors, combined with uniform air supply volume across the first to fourth floors, can maintain the average Predicted Mean Vote (PMV) of each floor within the range of −0.1 to 0.3. Conversely, excessive air supply volume on upper floors and insufficient air supply volume on lower floors significantly degrade the corridor thermal comfort.

Förderung

  • National Natural Science Foundation of China

Zitieren

APA

Zhao, G., Yang, J., Li, Z., & Zhao, J. (2026). CFD-Based Optimization of Air Conditioning Airflow Organization and Thermal Environment of Atrium–Corridor Spaces in an Office Building. Buildings, 16(9), 1817. https://doi.org/10.3390/buildings16091817

Vancouver

Zhao G, Yang J, Li Z, Zhao J. CFD-Based Optimization of Air Conditioning Airflow Organization and Thermal Environment of Atrium–Corridor Spaces in an Office Building. Buildings. 2026;16(9):1817. doi:10.3390/buildings16091817

BibTeX
@article{Zhao2026,
  author = {Zhao, Guoqiang and Yang, Jiahao and Li, Ziai and Zhao, Jing},
  title = {CFD-Based Optimization of Air Conditioning Airflow Organization and Thermal Environment of Atrium–Corridor Spaces in an Office Building},
  journal = {Buildings},
  year = {2026},
  volume = {16},
  number = {9},
  pages = {1817},
  doi = {10.3390/buildings16091817}
}
Kostenlos starten →