EUVIMEDEUVIMED entdecken
Open Access · CC BY 4.0

A Compact and Robust Framework for Multi-Condition Transient Pressure-Wave-Based Leakage Identification in District Heating Networks

Chang Chang, Xiangli Li, Xin Jia, Lin Duanmu

Buildings · 17.04.2026 · 16 (8) · 1586

DOI: 10.3390/buildings16081586 ↗

Kurz gefasst

Fachartikel in der Zeitschrift Buildings, online erschienen am 17.04.2026. Verfasst von Chang Chang und 3 weiteren Autor:innen. Die Arbeit nennt 52 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0).

AbstractBibliografische AngabenZitierenVerwandte Studien

Abstract (Originalsprache)

Leakage identification in district heating networks is challenging because leakage-induced transient pressure waves often overlap with pressure disturbances triggered by routine operations such as valve regulation, pump speed variation, and emergency shut-off. In addition, the scarcity of high-quality labeled leakage samples limits the robustness of data-driven models under small-sample conditions. To address these issues, this study proposes a compact and moderately interpretable framework for multi-condition identification from transient pressure-wave signals, integrating signal preprocessing, handcrafted statistical feature extraction, multiclass ReliefF-based feature selection, and class-wise generative adversarial network augmentation in the selected feature space. A dataset containing four representative conditions, namely leakage, valve regulation, pump speed regulation, and emergency valve shut-off, was constructed using an integrated indoor district heating network testbed. After Hampel-based spike suppression and zero-phase Butterworth band-pass filtering within 0.5 to 300 Hz, time- and frequency-domain statistical features were extracted, and a compact subset was selected by multiclass ReliefF. A class-wise generative adversarial network was then used to augment the training set in feature space, while all evaluations were performed strictly on real samples. The results show that feature-space augmentation improves robustness and generalization under operational disturbances and noise. Using random forest as the representative classifier, Accuracy and Macro-F1 increased from 0.960 to 0.985, while leakage recall improved from 0.920 to 0.980. Further comparisons confirmed that the ReliefF-selected subset outperformed representative alternatives such as LASSO and mRMR. Overall, the proposed framework provides an effective solution for distinguishing leakage events from operational disturbances and offers practical support for online monitoring and intelligent operation of district heating networks.

Zitieren

APA

Chang, C., Li, X., Jia, X., & Duanmu, L. (2026). A Compact and Robust Framework for Multi-Condition Transient Pressure-Wave-Based Leakage Identification in District Heating Networks. Buildings, 16(8), 1586. https://doi.org/10.3390/buildings16081586

Vancouver

Chang C, Li X, Jia X, Duanmu L. A Compact and Robust Framework for Multi-Condition Transient Pressure-Wave-Based Leakage Identification in District Heating Networks. Buildings. 2026;16(8):1586. doi:10.3390/buildings16081586

BibTeX
@article{Chang2026,
  author = {Chang, Chang and Li, Xiangli and Jia, Xin and Duanmu, Lin},
  title = {A Compact and Robust Framework for Multi-Condition Transient Pressure-Wave-Based Leakage Identification in District Heating Networks},
  journal = {Buildings},
  year = {2026},
  volume = {16},
  number = {8},
  pages = {1586},
  doi = {10.3390/buildings16081586}
}