Rethinking Winter Heating in University Classrooms in China’s Hot Summer and Cold Winter Regions: Setpoint–Preference Mismatches, Pre-Heating, and Comfort Assessment

Quyi Gong, Xin Ye, Xiaoyi Yang, Tao Zhang, Weijun Gao

Buildings · 25.03.2026 · 16 (7) · 1304

DOI: 10.3390/buildings16071304 ↗

Kurz gefasst

Fachartikel in der Zeitschrift Buildings, online erschienen am 25.03.2026. Verfasst von Quyi Gong und 4 weiteren Autor:innen. Die Arbeit nennt 55 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0). Gefördert von: Kangba Culture Research Center, a Key Research Base for Philosophy and Social Sciences in Sichuan Province, Modern Design and Culture Research Center, a Key Research Base for Philosophy and Social Sciences in Sichuan Province, Chengdu University.

AbstractBibliografische AngabenZitierenVerwandte Studien

Abstract (Originalsprache)

Winter thermal comfort in university classrooms in China’s Hot Summer and Cold Winter (HSCW) regions remains problematic due to mismatches between institutional heating setpoints and students’ actual thermal preferences. To investigate students’ thermal perceptions and behavioral responses, a post-occupancy evaluation (POE) survey was conducted, followed by field measurements in a typical classroom in Chengdu under three conditions: no-heating condition, heating conditions at 20 °C and 25 °C. Indoor environmental parameters were continuously monitored, and thermal comfort was assessed using the Predicted Mean Vote (PMV) and Predicted Percentage of Dissatisfied (PPD) model. The results show that no-heating conditions were unacceptable, highlighting the necessity of heating. While the 20 °C setpoint provided partial improvement, thermal comfort was not consistently achieved throughout the day. In contrast, the 25 °C setpoint maintained near-neutral conditions during most occupied periods. In addition, a pre-heating duration of approximately 30 min was found to be essential for reducing initial thermal discomfort. Overall, the findings indicate that fixed institutional heating standards may not adequately satisfy students’ thermal needs. Adaptive heating strategies that combine appropriate setpoints with sufficient pre-heating duration are therefore recommended to balance thermal comfort and energy efficiency in university classrooms in the HSCW regions.

Förderung

  • Kangba Culture Research Center, a Key Research Base for Philosophy and Social Sciences in Sichuan Province
  • Modern Design and Culture Research Center, a Key Research Base for Philosophy and Social Sciences in Sichuan Province
  • Chengdu University

Zitieren

APA

Gong, Q., Ye, X., Yang, X., Zhang, T., & Gao, W. (2026). Rethinking Winter Heating in University Classrooms in China’s Hot Summer and Cold Winter Regions: Setpoint–Preference Mismatches, Pre-Heating, and Comfort Assessment. Buildings, 16(7), 1304. https://doi.org/10.3390/buildings16071304

Vancouver

Gong Q, Ye X, Yang X, Zhang T, Gao W. Rethinking Winter Heating in University Classrooms in China’s Hot Summer and Cold Winter Regions: Setpoint–Preference Mismatches, Pre-Heating, and Comfort Assessment. Buildings. 2026;16(7):1304. doi:10.3390/buildings16071304

BibTeX
@article{Gong2026,
  author = {Gong, Quyi and Ye, Xin and Yang, Xiaoyi and Zhang, Tao and Gao, Weijun},
  title = {Rethinking Winter Heating in University Classrooms in China’s Hot Summer and Cold Winter Regions: Setpoint–Preference Mismatches, Pre-Heating, and Comfort Assessment},
  journal = {Buildings},
  year = {2026},
  volume = {16},
  number = {7},
  pages = {1304},
  doi = {10.3390/buildings16071304}
}
Kostenlos starten →