Experimental and Numerical Characterization of a Prefabricated Timber Facade with Integrated HVAC Unit
Buildings · 17.03.2026 · 16 (6) · 1177
DOI: 10.3390/buildings16061177 ↗Kurz gefasst
Fachartikel in der Zeitschrift Buildings, online erschienen am 17.03.2026. Verfasst von Barbara Messner und 6 weiteren Autor:innen. Die Arbeit nennt 28 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0). Gefördert von: EU Horizon 2020 INFINITE project.
Abstract (Originalsprache)
The built environment in the EU accounts for 40% of the total energy consumption and 36% of the total greenhouse gas emissions. To address the inefficiency of existing buildings, renovation could reduce their total energy consumption by 5–6% and lower carbon dioxide emissions by approximately 5%. A retrofit solution for existing buildings involves the use of lightweight prefabricated systems, some of which include integrated HVAC components that are able to enhance their functionality. Indeed, such prefabricated facade elements with integrated HVAC systems can represent a minimally invasive method for reducing the energy consumption of an existing building. To assess the potential of this approach, a full-scale mock-up of a prefabricated timber facade with integrated HVAC system was tested at the Facade System Interactions Lab (FSIL) of Eurac Research, Bolzano. The experimental data were used to develop a calibrated and validated 3D finite element model in COMSOL Multiphysics. The validated model was used to evaluate the facade’s thermal performance under standard heating conditions through a proposed equivalent thermal transmittance indicator (Ueq). Results show that the active facade achieves 0.07 W m−2 K−1, compared to 0.21 W m−2 K−1 for the passive facade with identical materials but without active components.
Förderung
- EU Horizon 2020 INFINITE project
Zitieren
APA
Messner, B., Gubert, M., Tamburrini, D., Avesani, S., Pernigotto, G., Gasparella, A., & Demanega, I. (2026). Experimental and Numerical Characterization of a Prefabricated Timber Facade with Integrated HVAC Unit. Buildings, 16(6), 1177. https://doi.org/10.3390/buildings16061177
Vancouver
Messner B, Gubert M, Tamburrini D, Avesani S, Pernigotto G, Gasparella A, et al. Experimental and Numerical Characterization of a Prefabricated Timber Facade with Integrated HVAC Unit. Buildings. 2026;16(6):1177. doi:10.3390/buildings16061177
BibTeX
@article{Messner2026,
author = {Messner, Barbara and Gubert, Martino and Tamburrini, Diego and Avesani, Stefano and Pernigotto, Giovanni and Gasparella, Andrea and Demanega, Ingrid},
title = {Experimental and Numerical Characterization of a Prefabricated Timber Facade with Integrated HVAC Unit},
journal = {Buildings},
year = {2026},
volume = {16},
number = {6},
pages = {1177},
doi = {10.3390/buildings16061177}
}