Fachartikel in der Zeitschrift Buildings, online erschienen am 21.08.2023. Verfasst von Ancuța Maria Măgurean und 1 weiteren Autor:innen. Die Arbeit wurde bisher 7-mal zitiert (Crossref) und nennt 29 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0). Gefördert von: Deutsche Gesellschaft für Internationale Zusammenarbeit.

AbstractBibliografische AngabenZitierenVerwandte Studien

Abstract (Originalsprache)

The purpose of this study was to analyze the indoor air quality, in particular, the CO2 level, in a real environment, within 16 apartments located in the municipality of Zalău, Romania, in five recently renovated multifamily buildings in which families live under normal conditions. Long-term monitoring was undertaken for 4.5 months, during the heating season of 2022–2023. A representative microclimate perspective was analyzed: the median value of the time fraction, which exceeded the Indoor Environment Quality Category I (IEQcat I) threshold for adults’ bedrooms was 82.30%. For children’s bedrooms, it was 75.65%, while for living rooms, it was 58.78%. When considering IEQcat IV, it was identified that for the bedrooms, the time fraction for which the threshold values were exceeded was still significant (median value of 45.37% for adults’ bedrooms and 50.14% for children’s bedrooms). Even if the indoor thermal comfort conditions increased, it was found that for almost half of the time, the bedrooms did not provide a health-safe indoor environment for the occupants due to inadequate ventilation, exceeding the health threshold values. Thus, it was identified that the ventilation of buildings is a key issue within the renovation process and, currently, is not properly undertaken for the mass renovation of existing multifamily residential buildings.

Förderung

  • Deutsche Gesellschaft für Internationale Zusammenarbeit

Zitieren

APA

Măgurean, A. M., & Petran, H. A. (2023). Analysis of Measured CO2 Levels through Long-Term Monitoring in Renovated Multifamily Buildings: A Common Case. Buildings, 13(8), 2113. https://doi.org/10.3390/buildings13082113

Vancouver

Măgurean AM, Petran HA. Analysis of Measured CO2 Levels through Long-Term Monitoring in Renovated Multifamily Buildings: A Common Case. Buildings. 2023;13(8):2113. doi:10.3390/buildings13082113

BibTeX
@article{Mgurean2023,
  author = {Măgurean, Ancuța Maria and Petran, Horia Alexandru},
  title = {Analysis of Measured CO2 Levels through Long-Term Monitoring in Renovated Multifamily Buildings: A Common Case},
  journal = {Buildings},
  year = {2023},
  volume = {13},
  number = {8},
  pages = {2113},
  doi = {10.3390/buildings13082113}
}
Kostenlos starten →