Fachartikel in der Zeitschrift Batteries, online erschienen am 25.06.2026. Verfasst von Yanbo Jia und 5 weiteren Autor:innen. Die Arbeit nennt 19 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0). Gefördert von: Research Project on Fire Safety of Electrochemical Energy Storage Systems, National Natural Science Foundation of China.

AbstractBibliografische AngabenZitierenVerwandte Studien

Abstract (Originalsprache)

In order to investigate the suppression effect of different extinguishing agents on lithium-ion battery fires in real confined spaces, a comparative experiment was conducted using aerosols, heptafluoropropane, and perfluorohexanone. In tests without any fire suppression measures, the peak heat release rate reached up to 69.09 kW, and a total of 8.05 MJ of heat was generated along with multiple deflagration events. Moreover, the heptafluoropropane and perfluorohexanone both effectively extinguished the flames with extinguishing times of 12 and 20 s, respectively. The aerosol agent caused a significant contraction of the flames, but it was unable to achieve complete extinguishment. Regarding cooling performance, the heptafluoropropane decreased the front surface temperature of the battery by 147 °C, while perfluorohexanone achieved a reduction of 230 °C. Additionally, the liquid-phase adhesion characteristics of perfluorohexanone enabled sustained cooling. A comprehensive comparison indicates that the perfluorohexanone agent exhibits outstanding performance in flame extinguishment, cooling efficiency, and the suppression of thermal propagation. Heptafluoropropane demonstrates rapid fire suppression and is suitable as a fast-response agent, whereas the aerosol requires a multi-discharge design to achieve reliable performance. Based on these findings, it is recommended that energy storage systems adopt a composite suppression strategy for fire protection.

Förderung

  • Research Project on Fire Safety of Electrochemical Energy Storage Systems
  • National Natural Science Foundation of China

Zitieren

APA

Jia, Y., Shi, C., Zhang, L., Tao, A., Hu, S., & Li, H. (2026). Experimental Study on Fire Suppression of Lithium-Ion Battery Module with Different Extinguishing Agents in Confined Space. Batteries, 12(7), 229. https://doi.org/10.3390/batteries12070229

Vancouver

Jia Y, Shi C, Zhang L, Tao A, Hu S, Li H. Experimental Study on Fire Suppression of Lithium-Ion Battery Module with Different Extinguishing Agents in Confined Space. Batteries. 2026;12(7):229. doi:10.3390/batteries12070229

BibTeX
@article{Jia2026,
  author = {Jia, Yanbo and Shi, Chaohui and Zhang, Lei and Tao, An and Hu, Sen and Li, Huang},
  title = {Experimental Study on Fire Suppression of Lithium-Ion Battery Module with Different Extinguishing Agents in Confined Space},
  journal = {Batteries},
  year = {2026},
  volume = {12},
  number = {7},
  pages = {229},
  doi = {10.3390/batteries12070229}
}
Kostenlos starten →